Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM00314
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/27/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The addition of the floor sink in the room with the 3 foot spas results in the 2" waste being overloaded. Reference Table 7-5, UPC 2003. 2. Coordinate details 1/P2.0 and 2/P2.0 with the floor plan. |
| 01/31/2006 | GBONILL1 | WWM | REVIEW | Needs Review |