Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM00314
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/18/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
01/18/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
01/19/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The controlling code is the 2003 UPC. 2. Show the location and size of the reduced pressure backflow preventer for the building water source. 3. Provide backflow protection for the pedicure chairs. 4. Provide descriptions and the applicable standards for the plumbing fixtures that are to be provided by the owner. 5. Clarify the two notes that call for "CONN 2"S TO (E) 2"S where the (E) building drain is also called out as an "(E) 4"S". 6. Show the size, route, and termination of the T&P relief for the water heater. 7. Provide an expansion tank for the water heater. |
01/19/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
01/19/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/19/2006 | JIM EGAN | FIRE | REVIEW | Approved | |
01/19/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
01/24/2006 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
01/24/2006 | GBONILL1 | WWM | REVIEW | Needs Review |