Permit Number: T06CM00314
Parcel: 12512080A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM00314
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
01/18/2006 TERRY STEVENS ZONING REVIEW Approved
01/19/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The controlling code is the 2003 UPC.
2. Show the location and size of the reduced pressure backflow preventer for the building water source.
3. Provide backflow protection for the pedicure chairs.
4. Provide descriptions and the applicable standards for the plumbing fixtures that are to be provided by the owner.
5. Clarify the two notes that call for "CONN 2"S TO (E) 2"S where the (E) building drain is also called out as an "(E) 4"S".
6. Show the size, route, and termination of the T&P relief for the water heater.
7. Provide an expansion tank for the water heater.
01/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
01/19/2006 ROBERT SHERRY WATER REVIEW Approved
01/19/2006 JIM EGAN FIRE REVIEW Approved
01/19/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/24/2006 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review
01/24/2006 GBONILL1 WWM REVIEW Needs Review