| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/04/2007 | MARTIN BROWN | FIRE | REVIEW | Denied | 1) Indicate container capacity (in water gallons) 2) Indicate type and location of vehicle protection 3) Show detail of signage 4) Provide cut sheets on tanks and safety precaution details 5) Refer to 2003 IFC table 3804.3 for required separation distances 6) Verify compliance with 2003 IFC section 3804.3.1, specifically distance from deisel tanks. 7) Indicate method of overfill protection 8) Be advised a separate permit for the tanks will be required by the Fire Department. |
| 04/05/2007 | WILDAN | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Completed | |
| 04/05/2007 | WILDAN | 3RD PARTY REVIEW-COMMERCIAL | AT 3RD PARTY OFFICE | Approved | |
| 04/10/2007 | SREEVES1 | ZONING | REVIEW | Needs Review |