| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/31/2006 | MARTIN BROWN | FIRE | REVIEW | Denied | Fire sprinklers required. Indicate on plans, along with hazard classification, standard to design sprinkler system to, design density and area of operation, and water flow information (available from fire dept. 791-3234) |
| 04/07/2006 | ANDREW CONNOR | NPPO | REVIEW | Denied | Submit NPPO plan or Application for Exception per DS 2-15.2.0.C |
| 04/07/2006 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | 1. Interior landscape borders are required along site boundaries of the adjacent residential properties per LUC 3.7.2-I. 2. One (1) canopy tree must be provided for every thirty-three (33) linear feet of the interior landscape border per LUC 3.7.2.4. 3. A 5' wall is required to screen vehicle use area from adjacent residential zoned properties per LUC Table 3.7.2-1. 4. Indicate square footage of all landscaped areas and calculation of the percentage of vegetative coverage per DS 2-07.2.2.2.g 5. Revise note regarding decomposed granite to indicate: All disturbed areas including adjacent right of ways shall be treated with ground cover such as decomposed granite to help reduce dust pollution per LUC 3.7.2.7. Indicate treatment for landscaped areas. 6. Landscape plan shall include irrigation specification design and layout per DS 2-06.5.4.A & DS 2-06.5.4.B including source of irrigation, sleeves for driveways and sidewalks, locations of valves, low-flow bubblers or drip irrigation. 7. Submit NPPO plan or Application for Exception per DS 2-15.2.0.C 8. Additional comments may apply. |
| 04/13/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Denied | To: George Holguin / ADC West DATE: April 18, 2006 FROM: Suzanne Bohnet Engineering Division SUBJECT: 3120 E. Adams St., Bldg. 2 New Apartments Site plan T06CM00236 (First Review) Grading plan T06BU00725 (First Review) T14S, R14E, Section 04 RESUBMITTAL REQUIRED: Site Plan and Grading Plan. The Site Plan (SP) and Grading Plan (GP) cannot be approved as submitted. Please include a response letter to the comments along with the corrected copies of the SP with your next submittal. Site Plan: 1. Please include the GP from the Drainage Statement as part of the sheets with the SP or include the information from the GP on the same sheet as the SP, labeling as "Site/Grading Plan". 2. Please provide the basis of bearings for the lot and the vertical datum used for elevations. 3. The sidewalk along the Right-of-Way (ROW) is required to be a minimum of 5 feet wide rather than the proposed 4 feet. Please modify. 4. The onsite pedestrian circulation paths require a minimum width of 4 feet, not 3 feet. Please modify. 5. It appears that drainage from the roof of the proposed structure will concentrate flow towards the proposed sidewalks located north of the proposed structure. 100% of the 10-year flow must be conveyed under the sidewalks via a scupper(s). Please provide supporting calculations to demonstrate compliance with DS 3-01.4.4. 6. Please show truncated domes on the sidewalk ramps and provide a detail for them. 7. Please list the estimated cut and fill quantities in cubic yards. 8. Please include the drainage patterns and finished grade spot elevations. 9. Please provide the dimensions from the street monument lines to the existing/proposed curbs, sidewalks, driveways and utility lines. 10. Please provide a centralized onsite refuse storage, collection and pickup area with service access per DS 6-01.2.2A. Include a detail of the dumpster enclosure. 11. If onsite refuse collection is not feasible, please contact John Clark for options. Be advised a Development Services Modification Request (DSMR) will be required in this event. 12. If onsite refuse collection is provided, then an 18-foot curb return radius is required for the driveway along Adams St. per DS 3-01.0 Figure 6. Grading Plan: 1. If you prefer to have separate sheets for the SP and the GP, please ensure the GP is clearly marked "Grading Plan". Be sure to include the comments below on the SP if a combined "Site/Grading Plan" sheet is preferred. 2. Water harvesting techniques shall be incorporated into the development by conveying rooftop drainage to designated water harvesting areas. Please address how water-harvesting techniques will be incorporated into the development. Refer to the newly adopted City of Tucson Water Harvesting Guidance Manual for design considerations. Copies of the above-referenced manual can be obtained from the Engineering Counter. Also, please add the following note: "Depress all landscaped areas a maximum of 6" for water harvesting". 3. A permit of a private improvement agreement will be necessary for any work performed within the ROW. Contact Permits and Codes at (520) 791-5100 for permit information. If you have any questions, I can be reached at 791-5550 x1188. Suzanne Bohnet, Engineer Associate Suzanne.Bohnet@tucsonaz.gov |
| 05/20/2006 | DAVID RIVERA | ZONING HC SITE | REVIEW | Denied | See Zoning Comments. |
| 05/20/2006 | DAVID RIVERA | ZONING | REVIEW | Denied | DSD TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: David Rivera Principal Planner PROJECT: T06CM00236 3120 E Adams St. Site Plan - Multi-Family Apartment Complex TRANSMITTAL DATE: May 20, 2006 COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. Please revise the location map as follows. A small, project-location map shall be drawn on the first sheet of the development plan, preferably in the upper right corner. The map should cover approximately one (1) square mile, be drawn at a minimum scale of 3" = 1 mile, and provide the following information. a. Show the subject property approximately centered within the one (1) square mile area. b. Identify conditions within the square mile area, such as major streets and watercourses. c. Section, township, and range; section corners; north arrow; and the scale will be labeled. DS 2-02.2.1.A.4 2. Please clarify if portions of the existing building are to be demolished. Staff has noticed a discrepancy in the drawing of the existing building with the 2005 aerial. Please submit copies of the last approved site plan and building plans for the existing building. Additional comments may be forthcoming on this issue. Label the building setbacks for the existing building from the east and north property lines. There may be a problem with the building setback between the proposed building and the existing building. Please verify with the commercial reviewers what the minimum setback between buildings must be. For clarity, please add the building heights on the elevation drawings for the top of ridge facing the west, top of plate for the second story facing the south and the height from finished grade to top of slab. Additional comments may be forthcoming based on response to zoning comments and revisions to the plan. DS 2-02.2.1.A.6 and DS 2-02.2.1.A.7 3. Off-street parking, including fully dimensioned layout, location, parking spaces' size and number, and dimensioned typical parking space details for both handicapped and standard spaces, together with access thereto must be added to the plan. The wheel stops must be dimensioned at 2.5 feet from the front of the space to the tire side of the stop. The parking calculation indicates that vehicle parking has been calculated for two 3-bedroom units and three 2-bedroom units. The number of bedrooms for the new units can be verified at this time. Until the requested floor plan for the existing residence is submitted for review, parking cannot be completely verified at this time. In addition to the required standard vehicle parking spaces, one van accessible parking space with an eight-foot wide access aisle must be provided. An access ramp at a 1:12 slope must be provided from the access aisle to the sidewalk. The ramp may not be placed within the access aisle. Revise the parking calculation to include the number of H.C. Parking spaces required and provided. Indicate by keynote the location of the van parking space sign. For consistency with the development standards, please dimension the back-up spur as detailed in Development Standards 3-05.2.2.D. DS 2-02.2.2.1.A.8 4. Add to the plan the off-street bicycle parking, including materials for lighting, paving, and security; fully dimensioned layout; location; specific type of rack and the number of bicycles it supports; and the location and type of directional signage. Add a bicycle parking calculation. Additional comments may be forthcoming on this item. DS 2-02.2.1.A.9 5. All sidewalks must be four feet in width. Revise the three-foot wide sidewalks to four feet. A sidewalk from the pedestrian circulation system has not been provided to the existing building. Please add the required four-foot sidewalk connecting from the pedestrian circulation to the existing building. Truncated Domes are required at all access ramps that transition onto vehicular use areas. DS 2-02.2.1.A.12 6. If applicable, draw, label, and dimension existing or proposed signs including billboards. DS 2-02.2.1.A.13 7. If applicable, draw, label, and dimension all existing or proposed easements. The recording information must be labeled for each easement. DS 2-02.2.1.A.20 8. Label the right-of-way dimensions from the roadway construction centerline to the curb and to the property line. DS 2-02.2.1.A.21 9. If applicable or proposed, indicate the location, type and height of freestanding lighting. DS 2-02.2.1.A.25 10. See the landscape reviewer comments regarding landscape border, screening, and NPPO requirements. DS 2-02.2.1.A.25 and .26 11. List as a note the existing and proposed use of the site. (Existing Use: Single Family Residence, Proposed Use: Multifamily Residential Use DD "K", Subject to LUC section 3.5.7.1.F.) DS 2-02.2.1.A.31 12. Indicate on the plan, the Refuse container location, size, and access thereto fully dimensioned. DS 2-02.2.1.A.32 13. Legends and symbols used in the preparation of the site plan shall be in accordance with City of Tucson Drafting Standards. Please add a legend listing symbols and line work used to prepare this drawing. DS 2-02.2.1.A.B 14. Revise or add the following development criteria items. a. The interior perimeter building setback is based on the greatest of 10 feet or the three quarters the height of the structure. Revise the perimeter note. b. Revise the vehicle parking requirements to include the handicapped parking spaces. c. Add a bicycle parking calculation. d. Revise the density calculation. The incorrect acreage has been used to calculate the number of units allowed. Revise as required. e. Revise the street building setback as to state that the setback is based on the greatest of 20 feet or one and one-half the height of the structure from the property line. If you have any questions about this transmittal, please call David Rivera, (520) 791-5608. DGR C:\planning\cdrc\DSD\T06CM00236.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/30/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |