Permit Number: T06BU00873
Parcel: 13413057F

Address:
51 S PANTANO RD

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T06BU00873
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2006 ANDREW CONNOR NPPO REVIEW Denied Submit a copy of the approved site plan including landscape and native plant preservation plans for reference. The grading application will be reviewed for compliance only when the approved documents are included in the submittal. Revise grading plans as necessary to comply with the approved site plan.
10/05/2006 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: FURR'S CAFETERIA - Southeast Corner of Broadway & Pantano
T06BU00873
Grading Plan (2nd Review)

TRANSMITTAL DATE: October 5, 2006

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please call Steve Shields,
(520) 791-5608 ext. 1180.

C:\planning\grading\t06bu00873-2nd.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plan and additional requested documents
10/30/2006 LOREN MAKUS ENGINEERING REVIEW Denied November 2, 2006
Site and Grading Review: Furr's Fresh Buffet
T06CM02086 and T06BU00873
Loren Makus, E.I.T.

The site and grading plans for the proposed Furr's Cafeteria at 51 S Pantano Road cannot be approved at this time. Since a complete drainage submittal was not provided with the site plan the plans cannot be approved at this time. Once a complete submittal is received, additional comments will be forthcoming. The following comments must be addressed:

Drainage Report Comment:

1. The submitted drainage report does not meet the standards of the City of Tucson. Provide a drainage report that addresses the requirements of the Standards Manual for Drainage Design and Floodplain Management in Tucson Arizona (SMDDFM) and the Stormwater Detention/Retention Manual (SDRM). Specifically refer to SMDDFM sections 2.3 and SDRM Chapter V. Additional information can be found in Chapter XIV of the SMDDFM.

Site/Grading Comments:

2. Provide a plan that is clearly marked as the site plan and that provides the information required by the City of Tucson Development Standard (DS) 2-02.0. All of the required elements must be provide on this plan.
3. As previously commented, show on the site plan the location of each driveway on each adjacent property. Driveways must be at least 80 feet apart on MS&R streets.. The measurement is taken at the point of tangency for the curb return.(Transportation Access Management Guidelines)
4. As previously commented, show on the site plan maneuverability for Solid Waste vehicle access to the compactor. The access must provide for 40 feet of clear, straight access to the compactor.

SWPPP comments:
The stormwater pollution prevention plan does not meet the minimum requirements of the construction general permit. The SWPPP must
5. Remove the statement that drywells will be installed from the sequence of events.
6. Identify the wash adjacent to the site as a receiving water. The wash is Owens Park Wash.
7. Part IV.B.2.c Explicitly indicate in the SWPPP the name of the operator with operational control over project specifications (including the ability to make modifications in specifications).
8. Part IV.B.2.c Explicitly indicate in the SWPPP the name of the operator with operational control over day-to-day activities at the construction site.
9. Part IV.C.2.a. Describe the project's intended use after NOT is filed
10. Part IV.C.2.d. Provide an estimate of the pre-construction runoff coefficient a
11. Part IV.C.2.e. Include a general location map (e.g. U.S.G.S. quadrangle, portion of a city or county map) showing 1 mile radius around site
12. Part IV.C.2.e. Include and identify receiving waters in the general location map.
13. Part IV.C.3.a. Identify on the map drainage patterns and estimated slopes after grading
14. Part IV.C.3.b. Identify on the map areas of soil disturbance Identify on the map areas not to be disturbed
15. Part IV.C.3.c. Identify on the map locations of structural and nonstructural controls identified in the SWPPP.
16. Part IV.D.2.a. Describe the erosion and sediment controls designed to retain sediment on site to the extent practicable. Provide clear descriptions and details for all inlet protection. Provide scheduling instructions as well.
17. Part IV.D.8.c. Describe BMPs for managing concrete truck washout and surplus concrete discharge. If concrete trucks are not allowed to wash out or discharge surplus concrete of drum wash water on site, provide a description of the program to be used to prevent such discharges from becoming pollutants elsewhere.
18. Part IV.F. Include copy of AZPDES permit (AZG2003-001), NOI and ADEQ authorization as part of the SWPPP
19. Part IV.J.1. Each Operator must sign the SWPPP
20. Tucson Code 26-42.b The SWPPP must be prepared and certified by an engineer or landscape architect.
21. Review all of the SWPPP document to ensure that it describes this project. For example, there are several references to drywells. No drywells have been proposed for this site.

If you have any questions about these comments or if you wish to set up a meeting contact me at 520.791.5550 Ext 1160 or at loren.makus@tucsonaz.gov.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/20/2006 DELMA ROBEY APPROVAL SHELF Completed
11/20/2006 DELMA ROBEY OUT TO CUSTOMER Completed
11/20/2006 SUE REEVES REJECT SHELF Completed