Permit Number: T06BU00873
Parcel: 13413057F

Address:
51 S PANTANO RD

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T06BU00873
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2006 ANDREW CONNOR NPPO REVIEW Denied 1. This project cannot be reviewed without a site plan. Submit a complete site plan which includes all required content, specifications, and calculations listed in DS 2-02.

2. Review will continue upon re-submittal of requested documents.

3. Additional comments may apply
07/25/2006 LOREN MAKUS ENGINEERING REVIEW Denied July 27, 2006
Site and Grading Review: Furr's Fresh Buffet
T06CM02086 and T06BU00873
Loren Makus, E.I.T.

The site and grading plans for the propoesed Furr's Cafeteria at 51 S Pantano Road cannot be approved at this time. Since a complete drainage submittal was not provided with the site plan the plans cannot be approved at this time. Once a complete submittal is received, additional comments will be forthcoming. The following comments must be addressed:

Drainage Report Comment:

1. The submitted drainage report does not meet the standards of the City of Tucson. Provide a drainage report that addresses the requirements of the Standards Manual for Drainage Design and Floodplain Management in Tucson Arizona (SMDDFM) and the Stormwater Detention/Retention Manual (SDRM). Specifically refer to SMDDFM sections 2.3 and SDRM Chapter V. Additional information can be found in Chapter XIV of the SMDDFM.

Site/Grading Comments:

2. Provide a plan that is clearly marked as the site plan and that provides the information required by the City of Tucson Development Standard (DS) 2-02.0. All of the required elements must be provide on this plan.
3. As previously commented, show on the site plan the location of each driveway on each adjacent property. Driveways must be at least 80 feet apart on MS&R streets.. The measurement is taken at the point of tangency for the curb return.(Transportation Access Management Guidelines)
4. As previously commented, the Stormwater Pollution Prevention Plan for this project does not meet the minimum requirements of the ADEQ Construction General Permit. ADEQ provides a checklist for SWPPP preparation. The SWPPP checklist can be obtained from the ADEQ website at: http://www.azdeq.gov/environ/water/permits/download/cswppp.pdf. Include a completed SWPPP checklist with the SWPPP. In the checklist clearly describe the location within the SWPPP for each required element. The completed SWPPP generally requires a report along with the site map subm
5. As previously commented, show on the site plan maneuverability for Solid Waste vehicle access to the compactor.

If you have any questions about these comments or if you wish to set up a meeting contact me at 520.791.5550 Ext 1160 or at loren.makus@tucsonaz.gov. I recommend that we meet before the plans are submitted again.
08/15/2006 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: FURR'S CAFETERIA - Southeast Corner of Broadway & Pantano
T06BU00873
Grading Plan (1st Review)

TRANSMITTAL DATE: August 15, 2006

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please call Steve Shields,
(520) 791-5608 ext. 1180.

C:\planning\grading\t06bu00873.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plan and additional requested documents

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
08/17/2006 SUE REEVES REJECT SHELF Completed