Permit Number: T05CM06409
Parcel: 137271960

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T05CM06409
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2007 DAVE MANN FIRE REVIEW Approved
01/05/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) CODE REVIEW TO REFLECT ACTUAL SQUARE FOOTAGE OF BUILDING (6842 SQ. FT.). SITE, FLOOR AND PLUMBING SITE PLANS SHOULD ALL SHOW SAME BUILDING AREA.

2) DEFERRED SUBMITTAL FOR TRUSS DRAWINGS MUST BE APPROVED BY BUILDING OFFICIAL.

3) CLARIFY APPLICATION OF KEYED NOTES ON PP S-3.

4) ROOF SHEATHING NOTE PP S-3 IMPLIES THAT ENTIRE ROOF IS BLOCKED. HATCHED AREA INDICATES THAT ONLY 14' ON EACH SIDE IS BLOCKED, PLEASE CLARIFY.

5) PLEASE ADD DETAIL FOR KEYNOTE 7 PP S-3.

6) YOUR CUT SHEET REFERENCES AND PLAN LEGEND REFER TO A PAGE S-5. DO YOU MEAN S-4? PLEASE CORRECT.
01/10/2007 TERRY STEVENS ZONING REVIEW Denied 01/10/07

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Building Plans: T05CM06363 & T05CM06409

Comments:

1. Zoning will review and approve the building plans once the site plan has been approved. Two approved and stamped copies of the approved site plan, landscape and NNPO plans must be included with the building plans.

2. Zoning will review and approve the building plans once the structural and commercial reviewers have approved the building plans.

If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000.
01/25/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The submitted COMcheck energy code calculations dated 12/05/06 show that the building envelope fails to meet the energy code requirements by 6%. Revise the design as required and resubmit new calculations. Energy calculations shall be sealed by the appropriate registrant and prepared by a bona fide employee under the registrant's direct supervision as defined by the Arizona State Board of Technical Registration's Rules & Regulations.
01/25/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/02/2007 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/06/2007 LOREN MAKUS ENGINEERING REVIEW Denied The following review comments are based on a building plan review. The building plan can not be approved prior to site plan approval. Please submit the city approved site plan with the building plan set. The approved site plan will have City of Tucson Fire, Zoning and Engineering stamps on this plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2007 DELMA ROBEY OUT TO CUSTOMER Completed
02/26/2007 SUE REEVES REJECT SHELF Completed