Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T05CM06409
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 01/05/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) CODE REVIEW TO REFLECT ACTUAL SQUARE FOOTAGE OF BUILDING (6842 SQ. FT.). SITE, FLOOR AND PLUMBING SITE PLANS SHOULD ALL SHOW SAME BUILDING AREA. 2) DEFERRED SUBMITTAL FOR TRUSS DRAWINGS MUST BE APPROVED BY BUILDING OFFICIAL. 3) CLARIFY APPLICATION OF KEYED NOTES ON PP S-3. 4) ROOF SHEATHING NOTE PP S-3 IMPLIES THAT ENTIRE ROOF IS BLOCKED. HATCHED AREA INDICATES THAT ONLY 14' ON EACH SIDE IS BLOCKED, PLEASE CLARIFY. 5) PLEASE ADD DETAIL FOR KEYNOTE 7 PP S-3. 6) YOUR CUT SHEET REFERENCES AND PLAN LEGEND REFER TO A PAGE S-5. DO YOU MEAN S-4? PLEASE CORRECT. |
| 01/10/2007 | TERRY STEVENS | ZONING | REVIEW | Denied | 01/10/07 Development Services Department Zoning Review Section Terry Stevens Lead Planner Building Plans: T05CM06363 & T05CM06409 Comments: 1. Zoning will review and approve the building plans once the site plan has been approved. Two approved and stamped copies of the approved site plan, landscape and NNPO plans must be included with the building plans. 2. Zoning will review and approve the building plans once the structural and commercial reviewers have approved the building plans. If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000. |
| 01/25/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The submitted COMcheck energy code calculations dated 12/05/06 show that the building envelope fails to meet the energy code requirements by 6%. Revise the design as required and resubmit new calculations. Energy calculations shall be sealed by the appropriate registrant and prepared by a bona fide employee under the registrant's direct supervision as defined by the Arizona State Board of Technical Registration's Rules & Regulations. |
| 01/25/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/02/2007 | BETSY COTTLE | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/06/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | The following review comments are based on a building plan review. The building plan can not be approved prior to site plan approval. Please submit the city approved site plan with the building plan set. The approved site plan will have City of Tucson Fire, Zoning and Engineering stamps on this plan. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/26/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 02/26/2007 | SUE REEVES | REJECT SHELF | Completed |