Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM06362
Parcel: 110121360

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM06362
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.provide a disconnect at the water heater. 2.Provide a maint. gfci protected receptacle for the roof top mechaical equipment as is required. 3.Provide emergency egress lighting at all required exterior exits. 4.Circuit BP-2 is improperly calculated. Please re-check load and correct circuit,panel,and service loads accordingly. Note: Please double check all the other circuits as they may need to be adjusted as well.( I did not review these other circuits at this time).

Final Status

Task End Date Reviewer's Name Type of Review Description
03/07/2006 AOLIVO1 OUT TO CUSTOMER Completed
03/07/2006 SUE REEVES REJECT SHELF Completed