Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.provide a disconnect at the water heater. 2.Provide a maint. gfci protected receptacle for the roof top mechaical equipment as is required. 3.Provide emergency egress lighting at all required exterior exits. 4.Circuit BP-2 is improperly calculated. Please re-check load and correct circuit,panel,and service loads accordingly. Note: Please double check all the other circuits as they may need to be adjusted as well.( I did not review these other circuits at this time).