Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T05CM06362
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2006 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.provide a disconnect at the water heater. 2.Provide a maint. gfci protected receptacle for the roof top mechaical equipment as is required. 3.Provide emergency egress lighting at all required exterior exits. 4.Circuit BP-2 is improperly calculated. Please re-check load and correct circuit,panel,and service loads accordingly. Note: Please double check all the other circuits as they may need to be adjusted as well.( I did not review these other circuits at this time). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/07/2006 | AOLIVO1 | OUT TO CUSTOMER | Completed |
| 03/07/2006 | SUE REEVES | REJECT SHELF | Completed |