Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05CM06362
Parcel: 110121360

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM06362
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
01/24/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the waste and vent diagram for Bath 1 to coordinate with the floor plan.
2. Show the required sizes for the mounting anchors of the water heater bracket.
3. Provide descriptions (e.g. standards from Chapter 14, 2003 UPC) of P-3 and P-4.
4. Provide water temperature control for the lavatories (not the water heater temperature control).
01/24/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the outside air quantity for AC5-2 per Section 403.3.2, IMC 2003.
02/09/2006 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review