Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM06362
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/24/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 01/24/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the waste and vent diagram for Bath 1 to coordinate with the floor plan. 2. Show the required sizes for the mounting anchors of the water heater bracket. 3. Provide descriptions (e.g. standards from Chapter 14, 2003 UPC) of P-3 and P-4. 4. Provide water temperature control for the lavatories (not the water heater temperature control). |
| 01/24/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the outside air quantity for AC5-2 per Section 403.3.2, IMC 2003. |
| 02/09/2006 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |