Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM06362
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2006 JIM EGAN FIRE REVIEW Approved
01/03/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The governing plumbing code is the 2003 UPC.
2. Provide a waste and vent riser diagram.
3. Show how the water piping was sized.
4. Provide heat traps and insulation for the inlet and outlet piping of the water heater. Reference Section 804, IECC 2003.
5. Show how the water heater platform is to be anchored to the wall.
6. Provide descriptions for the plumbing fixtures.
7. Verify the deletion of the floor drains.
8. Show how the water temperature to the lavatories will be controlled. Reference Section 804, IECC 2003.
01/03/2006 DAVE MANN ELECTRICAL-COMMERCIAL REVIEW Denied Fault current calculations are too small to read. Conductors used are too small for load.

2003 Energy Code only allows 1.1 or 1.2 (medical/clinical) watt/sf depending on use.

If medical treatment rooms independent ground is required.
01/03/2006 ROBERT SHERRY WATER REVIEW Approved
01/03/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The governing mechanical code is the 2003 IMC.
2. Revise the ventilation for the Group Room and the Waiting Room per Sections 403.3 and 403.3.2, IMC 2003.
3. Provide a sequence of operation for EF-1 and EF-2 to show that no recirculation of the air from the restrooms. Reference Section 403.2.1, IMC 2003.
4. Provide duct insulation per Section 803.2.8. SHow the minimum R-values on the drawings.
12/21/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
12/21/2005 GERRY KOZIOL WWM REVIEW Approved
12/21/2005 JWILLIA5 BUILDING-COMMERCIAL REVIEW Needs Review
12/21/2005 JOSE ORTIZ ENGINEERING REVIEW Approved