Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM06362
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2006 | JIM EGAN | FIRE | REVIEW | Approved | |
| 01/03/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The governing plumbing code is the 2003 UPC. 2. Provide a waste and vent riser diagram. 3. Show how the water piping was sized. 4. Provide heat traps and insulation for the inlet and outlet piping of the water heater. Reference Section 804, IECC 2003. 5. Show how the water heater platform is to be anchored to the wall. 6. Provide descriptions for the plumbing fixtures. 7. Verify the deletion of the floor drains. 8. Show how the water temperature to the lavatories will be controlled. Reference Section 804, IECC 2003. |
| 01/03/2006 | DAVE MANN | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Fault current calculations are too small to read. Conductors used are too small for load. 2003 Energy Code only allows 1.1 or 1.2 (medical/clinical) watt/sf depending on use. If medical treatment rooms independent ground is required. |
| 01/03/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/03/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The governing mechanical code is the 2003 IMC. 2. Revise the ventilation for the Group Room and the Waiting Room per Sections 403.3 and 403.3.2, IMC 2003. 3. Provide a sequence of operation for EF-1 and EF-2 to show that no recirculation of the air from the restrooms. Reference Section 403.2.1, IMC 2003. 4. Provide duct insulation per Section 803.2.8. SHow the minimum R-values on the drawings. |
| 12/21/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/21/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/21/2005 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/21/2005 | JOSE ORTIZ | ENGINEERING | REVIEW | Approved |