Permit Number: T05CM05879
Parcel: 141148150

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM05879
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The reply to the comment only addressed hot weather; how do the makeup air units comply with Section 508.1.1 when the outside air temperature is 32 degrees Fahrenheit? Provide information to show that the make up air for the kitchen hoods (MUA-1 and MUA-2) complies with Section 508.1.1, IMC 2000.
03/06/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The gas piping diagram indicates that the total gas load is 1177 CFH at a developed length of 250 feet. According to Table 12-3, a 2-1/2" pipe can only accommodate 1131 CFH, not 1177 CFH. Reference Section 1217.0, UPC 1994.
03/16/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved