Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T05CM05814
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Denied | To: MW2 Development DATE: January 11, 2006 FROM: Suzanne Bohnet Engineering Division SUBJECT: 3428 E. Bermuda St., Units 1 and 2 Site plan T05CM05814 (First Review) T13S, R14E, Section 33 RESUBMITTAL REQUIRED: Site Plan. The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal. Site Plan: 1) Please include a response letter to the comments along with the corrected copies of the SP. 2) The amount of cut and fill exceeds 50 cubic yards. A Grading Permit is required. Include with the submittal of a Grading Permit a Drainage Statement that explains how the drainage will be affected by the proposed development. The Drainage Statement should ensure that nuisance flows and/or adverse draining effects that are created by the proposed development will not create additional hazards for adjacent properties. The following are NOT required for the submittal of the Grading Permit: a) A Stormwater Pollution Prevention Plan (SWPPP). b) A Soils Report. c) A Floodplain Use Permit. 3) The font size used for the Site Data and the Notes on the SP need to be a minimum of 12 (0.12") point per D.S. 2-05.2.1C. The purpose of this requirement is to assure that all lettering is legible when reviewed and will maintain that legibility when reproduced and photographically reduced (microfilmed) for record-keeping purposes. 4) Please provide a small project-location map on the SP. 5) The descriptions for the existing residences 1 and 2 are written in pencil. Please provide that information in ink instead. 6) Please provide the basis of bearings and the basis of elevation, including the vertical datum used. 7) Please label the SVT. 8) The 2002 aerial photographs of this property show a structure in the location of the proposed duplex. Per Permits Plus, an entry exists stating a fire totally destroyed a house at 3426 E. Bermuda St. Is the proposed duplex replacing the structure that was destroyed by the fire? Please clarify. 9) Please provide the finished grades. 10) Please provide a legend or label the drainage flow arrows. 11) Please provide the dimensions from street monument lines to existing and/or proposed curbs, sidewalks, driveways and utility lines. 12) The SP depicts a 6" curb in front of the refuse container. Please clarify. 13) The orientation of the refuse container cannot be accepted due to the sanitation truck having to back out onto a public street. Please relocate the refuse container, providing adequate turn-around area. Alternatively, you may check with John Clark with Environmental Services at (520) 791-5414 ext. 1136. The proposed location may be approved through a potential Development Standards Modification Request (DSMR). 14) The sidewalk width needs to be 5', not 4'. Please adjust. 15) A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information. 16) As per Federal ADA requirements, all wheel chair ramps shall have the Truncated Domes instead of the standard grooves, which are shown on City of Tucson Standard Detail 207. Aside from the Truncated Domes, the wheel chair ramps shall be constructed in accordance with the Standard Detail 207. If you have any questions, I can be reached at 791-5550 x1188. Suzanne Bohnet, Engineer Associate City of Tucson / Development Services Department 201 N. Stone Avenue / P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 791-5550 x1188 office (520) 879-8010 fax |
| 01/28/2006 | DAVID RIVERA | ZONING HC SITE | REVIEW | Approved | |
| 01/28/2006 | DAVID RIVERA | ZONING | REVIEW | Denied | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: David Rivera Senior Planner PROJECT: T05CM05814 3428 E Bermuda St. No. 1 and 2 Site Plan - New Duplex and 2 existing Single Family residence buildings TRANSMITTAL DATE: January 28, 2006 COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. List as a note the legal description of the property. DS 2-02.2.1.A.2 2. Please clarify and revise if necessary the property address. The address on the site card is listed as 3428 E. Bermuda St. and the address on the site plan is listed as 3436 E Bermuda. Please revise accordingly. DS 2-02.2.1.A.3 3. A small, project-location map shall be drawn on the first sheet of the development plan, preferably in the upper right corner. The map should cover approximately one (1) square mile, be drawn at a minimum scale of 3" = 1 mile, and provide the following information. 1. Show the subject property approximately centered within the one (1) square mile area. 2. Identify conditions within the square mile area, such as major streets and watercourses. 3. Section, township, and range; section corners; north arrow; and the scale will be labeled. DS 2-02.2.1A.4 4. In addition to the property line distance information add the bearings for the property lines. DS 2-02.2.1.A.5 5. All existing and proposed buildings and structures, including location, size, height, overhangs, canopies, and use. It does not appear that the building footprints have been depicted on the plan as they exist on site. Indicate all existing porch structures, overhangs, carports, sheds etc and dimension the all the building footprints. Indicate the building height for each existing and proposed structure. Include in the next site plan submittal, dimensioned floor plan drawing of the existing buildings to verify the number of bedrooms and building square footages. DS 2-02.2.1.A.6 6. Vehicle parking is based on the number of bedrooms per unit. The required parking cannot be verified until the floor plans for all the buildings are provided for review. When the side(s) of a parking space abuts any vertical barrier over six (6) inches in height, other than a vertical support for a carport, the required width for the space is ten (10) feet to provide extra width to allow passengers to enter and exit the vehicle on the side where the barrier exists. The parking space adjacent to the dumpster enclosure must be designed to a ten-foot width. Label the width of the parking spaces. The minimum width requirement is eight and one half feet. Label and revise as required. DS 2-02.2.1.A.8 7. Bicycle parking is required for this development. Bicycle parking is based on a ratio of eight percent of the number of vehicle parking spaces provided. This site must be provided with a minimum of two class two bicycle parking spaces. Include in the parking calculations the number of bicycle parking spaces required and the number and class provided. Draw and label the location of the off-street bicycle parking facility, including materials for lighting, paving, and security; fully dimensioned layout; location; specific type of rack and the number of bicycles it supports; and the location and type of directional signage. Add a fully dimensioned detail drawing of the bicycle parking facility. DS 2-02.2.1.A.9 8. If applicable, draw and label the location, type, size, and height of existing and proposed freestanding signage including billboards. DS 2-02.2.1.A.13 9. If applicable indicate the location of existing or proposed freestanding lighting. The location, height and type of light pole proposed must be labeled. DS 2-02.2.1.A.25 10. Se the landscaper reviewer comments for information related to landscape borders, screening and NPPO requirements. DS 2-02.2.1A.27 11. Revise the use note to state the use as "Existing and proposed use is multi-family residential" DD "K", subject to LUC section 3.5.7.1.F. DS 2-02.2.1.A.31 12. The location of the refuse container and enclosure may no be an acceptable location. Please verify with the Engineering reviewer and the John Clark that the location of the Dumpster and enclosure will be acceptable. Ds 2-02.2.1.A.32 13. The site plan must be accompanied by a landscape plan with information specified in Development Standard 2-07.0. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. DS 2-02.2.2.C 14. Revise the vehicle parking calculations accordingly based on the number of bedroom per unit. Add the total and add the required number of parking spaces based on the overall requirement. Revise the zoning data code requirements as follows. The allowed and proposed density, the allowed and proposed/existing building heights, required and provided vehicle/bicycle parking spaces, allowed and actual lot coverage If you have any questions about this transmittal, please call David Rivera, (520) 791-5608. DGR C:\planning\cdrc\DSD\T05CM05814.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
| 12/20/2005 | JIM EGAN | FIRE | REVIEW | Denied | 1. A minimum 20 feet wide, paved, fire access roadway must be provided and extended to within 150 feet of all portions of the exterior walls of structures. An approved turnaround is required for dead-end access roadways. 2. Show location of nearest fire hydrant on plan. |
| 12/27/2005 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | 1. Submit a separate landscape plan per DS 2-07.0. To verify that entire site meets current minimum requirements. 2. Street landscape borders are required, a street landscape border, per Sec. 3.7.2.4 of the LUC, is a landscape area with a minimum width of ten (10) feet, running the full length of the street property line(s) bounding the site except for points of ingress-egress. 3. Fifty (50) percent or more of the street landscape border area must have shrubs and vegetative ground cover per LUC 3.7.2.4 4. One (1) canopy tree must be provided for every thirty-three (33) linear feet of landscape border per LUC 3.7.2.4. 5. Interior landscape borders are required along site boundaries of adjacent residential properties per LUC 3.7.2-I 6. Indicate square footage of all landscaped areas and calculation of the percentage of vegetative coverage per DS 2-07.2.2.2.g 7. The planting plan and layout calculations will include the following Information: · Both the proper and common name of each type of plant material must be listed. · Locations, size, and name of all existing vegetation to remain in place. · All disturbed areas including adjacent right of ways shall be treated with ground cover such as decomposed granite to help reduce dust pollution per LUC 3.7.2.7. Indicate treatment for landscaped areas. 8. A 30" continuous screen along street frontages for vehicle use area must be provided per LUC Table 3.7.2-I 9. A 5' wall is required to screen vehicle use area from adjacent residential properties per LUC Table 3.7.2-I. All walls required by this Division must be of masonry material or masonry with a stucco or textured finish. 10. All required screen walls must be located on-site or a joint use agreement shall be provided. Verify if existing walls are located within property lines 11. Within vehicular use areas, one (1) canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.a 12. Landscaping along parking lots where plants are susceptible to injury by vehicular traffic must be protected by appropriate means, such as curbs, bollards, or low walls per LUC 3.7.2.3.B 13. Landscape plan shall include irrigation specification design and layout per DS 2-06.5.4.A & DS 2-06.5.4.B including source of irrigation, sleeves for driveways and sidewalks, locations of valves, low-flow bubblers or drip irrigation. 14. Submit NPPO plan or Application for Exception per DS 2-15.2.0.C 15. Additional comments may apply |
| 12/28/2005 | ANDREW CONNOR | NPPO | REVIEW | Denied | Submit NPPO plan or Application for Exception per DS 2-15.2.0.C |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/02/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 02/02/2006 | SUE REEVES | REJECT SHELF | Completed |