12/15/2005 GERRY KOZIOL WWM REVIEW Denied 1:need to build public sewer.
2:needs wastewater IWC review-Tom Tomchak 579-5771
3:needs wastewater credit evaluation if applicable. Was exsisting facility connected to septic?
12/20/2005 MICHAEL ST. PAUL ZONING REVIEW Denied Copy of a stamped approved site plan is required.
12/27/2005 LOREN MAKUS ENGINEERING REVIEW Denied DATE: December 14, 2005
TO: HW BUD ACTIPIS for THREE DOG DANCER LLC
SUBJECT: 2420 N JACKRABBIT AV Building Addition Floodplain Preliminary Review
LOCATION: T13S R13E Section 34
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBERS: T05OT02600 / T05CM05118

PRELIMINARY FLOODPLAIN USE PERMIT REVIEW:
1) Tucson Code Section 26-11.2.(a): A preliminary review of your application for a floodplain use permit was performed. The application is not complete. Since the site may be affected by a jurisdictional flood, the floodplain ordinance compliance is required for this project. However, no drainage information was provided in the submittal package. A Drainage Report or sufficient drainage or hydrology study, is needed for the review of this Floodplain Use Permit submittal. The report should include FEMA discussion, erosion and/or flood protection improvements, as well as other necessary drainage information as listed in this section of the code as well as section of the Development Standards.
2) Tucson Code 26-11.2.(a)(1): Submit 3 sheets of the grading plans drawn to scale, showing the nature, location, dimensions and elevation of the lot, existing or proposed structures, fill, storage of materials, floodproofing measures, and the relationship of the above to the location of any watercourse channel, floodway, regulatory floodplain, erosion hazard area boundaries, and the regulatory flood elevation of the structures. All elevations or vertical distances must be referenced to an established datum or base elevation.
3) Tucson Code 26-4.1(a)(1): In order to determine substantial improvement in a flood hazard zone, submit monetary assessment of the project that includes the proposed improvements of the building addition, along with the value of the existing structure. See the following website for more information: http://www.floods.org/Certification/is9/unit8.pdf See especially pages 8-5 through 8-8.

Engineering Division of Development Services Department will generate a full review of the submittal package for T05CM05118 and T05OT02600 after the above preliminary comments are addressed. If you have questions please call me at 791-5550 extension 2204.

Elizabeth Eberbach, PE, CPM
Civil Engineer
Engineering Division
Development Services Department
12/27/2005 LOREN MAKUS ENGINEERING REVIEW Denied The building plan cannot be approved until the site plan has been approved.