Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM04672
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/26/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the RPBP to comply with the requirements of Section 610.2, UPC 1994. 2. Coordinate the waste and vent riser diagram to correspond to the floor plan. Note that P-1A will require a cleanout. |
09/26/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the exterior duct is insulated per Section 804, IECC 2000. 2. Provide a sequence of operation for the exhaust fan in the existing restroom to show that no recirculation of the supply air will occur. |
09/28/2005 | KMEDINA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/28/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |