| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/26/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the RPBP to comply with the requirements of Section 610.2, UPC 1994. 2. Coordinate the waste and vent riser diagram to correspond to the floor plan. Note that P-1A will require a cleanout. |
| 09/26/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the exterior duct is insulated per Section 804, IECC 2000. 2. Provide a sequence of operation for the exhaust fan in the existing restroom to show that no recirculation of the supply air will occur. |
| 09/28/2005 | KMEDINA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |