Permit Number: T05CM04672
Parcel: 12213221B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04672
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2005 JIM EGAN FIRE REVIEW Approved
09/12/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the size of the gas pipe branch to the water heater per Table 12-3, UPC 1994. Clarify the capacity of ACU1; it is shown as 108 MBH on M101 and 107 CFH on P101.
2. Provide upper terminal cleanouts for all fixtures with horizontal waste piping in excess of five feet.
3. Revise the font on the drawing for clarity; some fixture callouts and gas loads are illegible.
4. Revise the water pipe sizing to correspond to the submitted calculations. Note: provide the manufacturer and model number of the RPBP to verify the pressure drop shown in the calculations.
5. Provide the listing and operational information for the water heater.
6. Clarify the nature of P136 and the number of water and waste fixture units being assigned to it.
09/12/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
09/12/2005 ROBERT SHERRY WATER REVIEW Approved
09/12/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the water heater is to be vented.
2. Show that the duct is insulated per Section 804, IECC 2000.
3. Provide a sequence of operation for the exhaust fan in the existing restroom to show that no recirculation of the supply air will occur.
09/13/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) VALUATION FOR PROJECT.
2) STRUCTURAL CALCULATIONS FOR OPENING IN EXTERIOR WALL.
3) SPECIAL INSPECTION FOR EPOXY ANCHORS.
4) DOOR 104 ACCESSIBLE PER ANSI A117.1 2003.
09/13/2005 JOSE ORTIZ ENGINEERING REVIEW Approved
09/13/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
09/26/2005 GERRY KOZIOL WWM REVIEW Approved