Permit Number: T05CM04557
Parcel: 14042063C

Address:
6667 S TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T05CM04557
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2005 JIM EGAN FIRE REVIEW Approved
09/08/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 1994 Uniform Plumbing Code with Arizona State Amendments.
2. Provide an additional cleanout for the existing building sewer (maximum spacing of 100 feet) per Section 719.1, UPC 1994.
3. Specify the materials to be used for the water piping and fittings. Reference Section 604.1, UPC 1994.
09/08/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/08/2005 ROBERT SHERRY WATER REVIEW Approved
09/15/2005 DAN CASTRO ZONING REVIEW Denied Building plans may not be approved by the Zoning Review Section prior to site plan approval and building plan approval by Structural Review.
09/26/2005 GERRY KOZIOL WWM REVIEW Denied needs wastewater-iwc-Tom Tomchak-review of oil & sand separator- 579-5771.
need WW/8th floor, Ilene Deckard review- future lot split will change address and require joint use agreements.
09/29/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied
10/05/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied Approved site plan required prior to building plan approval.
10/11/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 10/11/05
ACTIVITY NUMBER: T05CM04557
PROJECT NAME: Truck wash canopy
PROJECT ADDRESS: 6667 S. Tucson Blvd.
ARCHITECT / ENGINEER: James Harrington
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Demolition permit must be purchased for existing building, concrete pad, canopy, and metal shed.
2) Provide a completed code analysis justifying seperated / non-seperated use (302.3.1) , therefore clarifying if fire seperation is required between buildings.
3) Special Inspection forms must be submitted before a permit can be issued.
4) Site plan must be approved before the building permit can be approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2005 JMORALE1 OUT TO CUSTOMER Completed
10/20/2005 SUE REEVES REJECT SHELF Completed