Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM04183
Parcel: 11820072C

Address:
317 W 23RD ST #4

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T05CM04183
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2005 JIM EGAN FIRE REVIEW Approved
08/15/2005 ROBERT SHERRY WATER REVIEW Approved
08/15/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide updated energy code compliance calculations. Reference Section 101.3, International Energy Conservation Code 2000.
2. Provide information to show that the commercial clothes dryer is being installed in conformance with the manufacturer's instructions. Reference Section 504.7, IMC 2000.
3. Revise detail 3/M1 to show a minimum of 6" of clearance from the vent and combustible construction.
4. Show that adequate make up air is being provided for the commercial clothes dryer.
5. Revise the termination of the water heater vent to conform with the requirements of Section 517.3, UPC 1994.
08/16/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a riser diagram for the new gas piping. Reference Section 103.2.3, UPC 1994.
2. Show that the gas sleeve and vent (detail 5/P2.1) complies with Section 1211.3, UPC 1994 as amended by the State of Arizona. Include both ends of the sleeve in the detail and indicate the relationship of the sleeve to the structures.
3. Coordinate the plumbing fixture schedule with the riser diagram, 5/P2.1, with regard to the number of hose bibbs being installed.
4. Show how the ceramic tile basin is allowable as a plumbing fixture and if so, how the specified drain complies with Section 410.1, UPC 1994. Reference Section 406.2, UPC 1994.
5. Show how the new water piping relates to the existing water supply system and show that the additional connections do not cause the existing piping to be overloaded. Reference Section 101.5.1, UPC 1994.
6. The new pressure-assisted water closets (and possibly the icemaker also) require a minimum pressure of 20 PSI. Is the existing water system able to accommodate this requirement? Reference Section 103.2.3, UPC 1994.
7. Show how the new water pipes were sized. (Include all fixtures and the water requirements of the HVAC equipment when calculating the total demand and determining pipe sizes.) Reference Section 610.1, UPC 1994.
8. The fixture connection sizes called out for the flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference Section A 6.1, UPC 1994 and IAPMO IS 3-93, Section 610.0.
9. Provide utility information about the new dishwasher and show that the installation will not overload the existing water supply or drainage systems. Reference Section 103.2.3, UPC 1994.
10. Provide an upper terminal cleanout for P8. Reference Section 707.4, UPC 1994.
08/29/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. New Clothes Dryer is 120V according to Sheet E-3, but is on 208V on the panel schedule. Please clarify.
2. The circuit designation D-8,10 is used 3 times on the Partial Electrical Plan. This does not correspond with the circuit designations on Panel D.
3. Demonstrate compliance with the disconnect requirements of NEC 422 Part III, for UH2.
4. Kitchen receptacles shall be GFCI. Reference NEC 210.8 (B) (3).
5. Please provide load calculations for Gutter #1 and its feeder.
6. Please note that the fault calculations are based on 240V, whereas this is a 208V system.
7. Please define the series rating indicated on Panel D Schedule. Specify the line side OCPD and its rating, and the load side device(s) and its(their) rating.
8. Basis for fault calculations corresponds to that on TEP SR-510 for 240V services. This is 208V. And since the TEP source apparently powers more than one service, AFC at both services may be affected. If the TEP developer has provided you with the 31900AFC figure for this particular installation, disregard.
9. Demonstrate compliance with the 2000 IECC.
08/31/2005 GERRY KOZIOL WWM REVIEW Approved
09/03/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/12/2005 DAN CASTRO ZONING REVIEW Denied Zoning Review may not approve the structural plans prior to Building Review approval.
09/13/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 9/19/05
ACTIVITY NUMBER: T05CM04183
PROJECT NAME: Laundry & Restrooms
PROJECT ADDRESS: 317 W. 23rd St.
ARCHITECT / ENGINEER: Robert Vint
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Clarify / Justify per Chapt. 3 Separated use, non-separated use, accessory use area.
2) Restroom @ laundry room does not meet the ANSI A117.1 2003 requirements. Show all clear floor space requirements on the documents.
3) Clarify accessible path to laundry room.
4) Provide complete structural analysis per Chapt 16 2003 IBC. Provide justification for masonry lintel design.
5) Clarify exiting for existing office building that storage door is not necessary for a exit of existing building. See code section 1013.2
6) Sht. A3.0 dtl. 4 - kitchen floor plan clarify clear floor space requirements for fixtures and turning radius.
7) Epoxy paint not acceptable finishes per section 1210.2 IBC.
8) Detail guard rail per section 1012.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2005 GBONILL1 OUT TO CUSTOMER Completed
10/04/2005 SUE REEVES REJECT SHELF Completed