Permit Number: T05CM04138
Parcel: 12108063A

Address:
1519 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04138
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/16/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 12/19/05
ACTIVITY NUMBER: T05CM04138
PROJECT NAME: RETAIL
PROJECT ADDRESS: 1519 N. Wilmot Rd.
ARCHITECT / ENGINEER: L. GENE ANDRES
PROJECT REVIEWER: CHRISTY FOREMAN


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Clarify on site plan total sq. footage of bldg. to justify under allowable 9000 sq. ft.
2) Justify 20% cost of construction being spent toward accessibility requirements per code section 3409.6 IBC 2003. Provide itemized breakdown of costs for items on the drawings.
3) Storefront door cannot be locked if it appears to be a exit it must operate as a exit.
4) Doors for storage room 106 and restroom 103 do not comply with code section 1005.2, please justify.
12/19/2005 JIM EGAN FIRE REVIEW Approved
12/27/2005 GERRY KOZIOL WWM REVIEW Passed
12/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide the minimum plumbing facilities required by Table 2902.1, IBC 2003, for mercantile occupancy.
12/28/2005 ROBERT SHERRY WATER REVIEW Approved
12/28/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations demonstrating adequate ventilation. Reference Sections 401.2, 403.3, and 403.3.2, IMC 2003.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/17/2006 JMORALE1 OUT TO CUSTOMER Completed
01/17/2006 SUE REEVES REJECT SHELF Completed