Permit Number: T05CM03734
Parcel: 117031120

Address:
847 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03734
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
07/14/2005 ANY BUILDING-COMMERCIAL REVIEW Approved
07/14/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
07/15/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/15/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM03734 7/14/05

1. Minimum font size 1/8".
2. Provide power requirements for outline lighting.
3. Demonstrate that Panel A is not overloaded.
4. Provide a disconnect for the outline lighting per NEC 600.6.
07/15/2005 GERRY KOZIOL WWM REVIEW Passed
07/15/2005 JIM EGAN FIRE REVIEW Approved
07/15/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/15/2005 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/15/2005 KMEDINA1 OUT TO CUSTOMER Approved