| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/14/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 07/14/2005 | ANY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/14/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/15/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/15/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM03734 7/14/05 1. Minimum font size 1/8". 2. Provide power requirements for outline lighting. 3. Demonstrate that Panel A is not overloaded. 4. Provide a disconnect for the outline lighting per NEC 600.6. |
| 07/15/2005 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 07/15/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/15/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 07/15/2005 | ROBERT SHERRY | WATER | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/15/2005 | KMEDINA1 | OUT TO CUSTOMER | Approved |