Permit Number: T05CM03285
Parcel: 12111022A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM03285
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied +.. T05CM03285 -2 .. 4927 EAST SPEEDWAY BOULEVARD .. VERIZON WIRELESS - WIRELESS TELEPHONE SWITCHING CENTER .. DGL .. 3RD REVIEW .. 3/27/06 ..

S1. See prior comment S1. Clarify Detectable Warnings ; locations at curbs, and curb ramps as well as specifications for the Detectable Warnings themselves using truncated domes. [S1. See prior comment S3. Provide 5'0 x 5'0 level landings at top and bottom of sidewalk corners to allow turns, provide 1:12 max slope ramps in straight runs of sidewalk to facilitate changes in grade, provide truncated dome detectable warning surfaces (24" x 5'0 strip on street side of landing), locate curbs so as not to inhibit accessibility, ref dwgs A1.1, A2.1, C-3, C-4, L-1, L-2, see ANSI -A117.1 - 2003ed, Sections 405 and 705. (S3. Revise sidewalks on Speedway to conform to Code as part of accessible route.)]
S2. See prior comment S5. [S5. See prior comment S30. Provide completed inspection program. (S30. Provide an inspection program per 1997 Uniform Administrative Code Section 302.5.)]
S3. See prior comment S6. [S6. See prior comment S31. Provide required Special Inspections. (S31. Special inspection is required for:
1. Masonry.
2. Epoxy anchors.
3. Field welding.
4. Soils.
5. Concrete.
6. High strength bolting.
7. Shop welding.
8. Steel.
9. Foundations.)]


Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.