Permit Number: T05CM03285
Parcel: 12111022A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM03285
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2006 GERRY KOZIOL WWM REVIEW Denied RECOUNTED ALL PLUMBING FIXTURES- NEEDS WASTEWATER 8TH FL CREDIT EVALUATION- NEEDS TO IDENTIFY SIZE OF EXISTING CONNECTION TO PUBLIC SEWER (PREVIOUS PERMITS)
01/09/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied Approved site plan is required prior to building plan approval.
01/12/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8 inch. Reference Section 302.3, Uniform Administrative Code, 1997.
2. Please address electrical load for PORT GEN DISCONNECT on Ckt ELP1-9,11.
12/16/2005 HEATHER THRALL ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Heather Thrall Senior Planner FOR: David Rivera Principal Planner


PROJECT: T05CM03285
4927 E. Speedway Blvd.
Verizon Cellular Phone Utility Station Expansion
Site plan 2nd Review
Transmittal date: December 15, 2005



COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1 This plan was reviewed by zoning staff for compliance with the last submitted and reviewed site plan. As the site plan has not been approved, and Board of Adjustment parking variances are required to allow the project to proceed, zoning staff cannot approve the building plans at this time.

2. This building plan may be reviewed over the counter, upon approval of the site plan. Please include copies of the approved site plan stapled into each set of building drawings. Should you have any questions on this review, please contact me via email at Heather.Thrall@tucsonaz.gov or at 520-791-4541x1156.


If you have any questions about this transmittal, please call (520) 791-5608.
12/19/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8 inch. Reference Section 302.3, Uniform Administrative Code, 1997.
2. Show the sequence of operation for exhaust fans EF-8 and EF-9 (continuous operation) on the drawings, to show that the recirculation of ventilation air from the restrooms will not occur. Reference Table 403.2.1 (3), IMC 2000.
3. Provide continuous ventilation for the battery room (Room 112) per Section 502.4.2, IMC 2000. Note: the requirement is 1 CFM per square foot of room area.
12/19/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8 inch. Reference Section 302.3, Uniform Administrative Code, 1997.
2. Clarify why water has been piped to the location of a bottled water cooler.
3. Finish labeling the pipe sizes on the waste and vent isometric (e.g. the mop sink, the bar sink, the existing floor drain, and the vents).
4. Show the location of the existing floor drain (noted on the waste and vent isometric) on the floor plan. Show the vent for the existing floor drain on the waste and vent isometric.
12/21/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied +.. T05CM03285 -1 .. 4937 EAST SPEEDWAY BOULEVARD .. VERIZON WIRELESS - WIRELESS TELEPHONE SWITCHING CENTER .. DGL .. 2ND REVIEW .. 12/28/05 ..

S1. See prior comment S3. Provide 5'0 x 5'0 level landings at top and bottom of sidewalk corners to allow turns, provide 1:12 max slope ramps in straight runs of sidewalk to facilitate changes in grade, provide truncated dome detectable warning surfaces (24" x 5'0 strip on street side of landing), locate curbs so as not to inhibit accessibility, ref dwgs A1.1, A2.1, C-3, C-4, L-1, L-2, see ANSI -A117.1 - 2003ed, Sections 405 and 705. (S3. Revise sidewalks on Speedway to conform to Code as part of accessible route.)
S2. See prior comment S4. No sprinkler increase for this partially sprinklered building. (S4. Clarify Allowable Area Calculation on Code Review Checklist explain fire-sprinkler increase for a partially fire-sprinklered building.)
S3. See prior comment S13. Clarify shear transfer at new lintels attached to existing masonry walls. [S13. Provide details of connection from new to existing :
1. Footings ( 2D, 3B, 3C, 4E,5E).
2. Masonry walls (2D, 3B, 4.2E, 4.9E).
3. Masonry lintels(3C, 4E, 5E).]
S4. See prior comment S16. 1. The first accessible parking space is required to be van accessible ANSI A117.1 Section 502 with proper signage, and as such requires the access aisle to be on the passenger side of the vehicle, 2. Provide adequate number of spot grade elevations to show Accessible Route grades conform to required slopes and level landings, revise site plan to comply. (S16. Indicate Accessible Route on drawings per IBC Section 1104.)
S5. See prior comment S30. Provide completed inspection program. (S30. Provide an inspection program per 1997 Uniform Administrative Code Section 302.5.)
S6. See prior comment S31. Provide required Special Inspections. (S31. Special inspection is required for:
1. Masonry.
2. Epoxy anchors.
3. Field welding.
4. Soils.
5. Concrete.
6. High strength bolting.
7. Shop welding.
8. Steel.
9. Foundations.)


Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/17/2006 GBONILL1 OUT TO CUSTOMER Completed
01/17/2006 GBONILL1 REJECT SHELF Completed