Permit Number: T05CM03285
Parcel: 12111022A

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T05CM03285
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2005 JIM EGAN FIRE REVIEW Approved
11/16/2005 ANDREW CONNOR NPPO REVIEW Approved
11/16/2005 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. An approved site plan is required indicating how the project will comply with LUC requirements when the MS&R right-of-way can no longer be used as part of the site. Such plan is to be an exhibit to an executed covenant for recordation stating the responsibility of the property owner, successor, or assignee as to the removal of improvements and compliance with the LUC at no cost to the City per LUC 2.8.3.5.F. A variance has been sought to decrease the number of parking spaces required, additionally the number will have to be reduced when future improvements are implemented, show how the site will meet parking requirements in the future, include any BOA documentation with re-submittal.
11/21/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: November 21, 2005
ACTIVITY NUMBER: T05CM03285
PROJECT NAME: Verizon Wireless
PROJECT ADDRESS: 4927 East Speedway Blvd.
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN


1. A Development Standard Modification Request is required for the proposed location of the solid waste enclosure. Contact Patricia Gehlen at 791-5550, ext. 1179, for submittal requirements.

2. In the site plan keynotes, keynote 3 denotes a request for a DSMR on the curb returns. Is this a typo? Is a DSMR being processed? If a DSMR has been approved for this project the activity number and the written decision must be on the site plan.

The above comment is from the first review. The response to this comment is the curb return variance will be requested from the Board of Adjustments. Contact the Traffic Engineering Division, Dale Kelch, 791-4259, for written approval.
12/13/2005 HEATHER THRALL ZONING REVIEW Denied DSD TRANSMITTAL
FROM: Heather Thrall, Senior Planner
FOR: David Rivera Principal Planner
PROJECT: T05CM03285
4927 E. Speedway Blvd.
Verizon Cellular Phone Utility Station Expansion
Site plan
Transmittal date: December 15, 2005
2nd Review

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This project encompasses 3 (three) proposed building additions for Verizon Wireless, a telephone utility company, at 4927 E. Speedway Boulevard. The total proposed square footage of the building is 8,681 square feet. Per 3.3.4 of the LUC, 1 (one) parking space is required per 500 square feet of gross floor (building) area for this development. A minimum of 17 (seventeen) parking spaces are required for the project to meet the stated code criteria. The submitted site plan shows only 10 (ten) parking spaces are proposed for this development, thus a Board of Adjustment variance is required to delete 7 (seven) parking spaces to meet current code requirements.

2. The total future right of way for Speedway Boulevard is 120 feet, per the City of Tucson Major Streets and Routes map. The project includes a future site plan indicating how the site will be developed once the future right of way expansion is completed. The future site plan indicates the deletion of 5 (five) parking spaces, leaving the site a total of 5 (five) parking spaces. This proposal requires a future Board of Adjustment variance to allow a total deletion of 12 (twelve) parking spaces from the site, based upon the proposed total Gross Floor Area of 8,681 square feet (Section 3.3.4 of LUC).

3.If a Board of Adjustment variance is granted, please note the case number, date of approval, variance(s) granted, and conditions imposed on the site plan. To obtain zoning review approval for the project, please return with a copy of the official Board of Adjustment decision memorandum and plans.


4. Per DS 2-02.2.1.20, easements must have recording docket and page references presented on the plan. Please provide this information for both utility easements shown at the north end of the site. This information must be provided prior to staff approval of the plan, even with issuance of the Board of Adjustment variances described above.


5. Depending upon the information provided in response to this review, further zoning review comments may be forthcoming. Should you have any questions on this review, please contact me via email at Heather.Thrall@tucsonaz.gov or at 520-791-4541x1156.


If you have any questions about this transmittal, please call (520) 791-5608.
12/15/2005 HEATHER THRALL ZONING HC SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/17/2006 GBONILL1 OUT TO CUSTOMER Completed
01/17/2006 SUE REEVES REJECT SHELF Completed