Permit Number: T05CM02730
Parcel: 141148150

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02730
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2005 JIM EGAN FIRE REVIEW Approved
06/14/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Based on the provided calculations, a 1/2" water line can only handle about 3 fixture units. Show what other fixtures are served by the same water lines as the new handf sink located in the existing storage area.
06/14/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/14/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
06/14/2005 ROBERT SHERRY WATER REVIEW Approved
06/14/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Passed
06/15/2005 GBONILL1 WWM REVIEW Needs Review
06/15/2005 GBONILL1 ZONING REVIEW Needs Review
06/15/2005 GBONILL1 ENGINEERING REVIEW Needs Review