Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02730
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/14/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/14/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Based on the provided calculations, a 1/2" water line can only handle about 3 fixture units. Show what other fixtures are served by the same water lines as the new handf sink located in the existing storage area. |
| 06/14/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/14/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/14/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 06/14/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/15/2005 | GBONILL1 | ZONING | REVIEW | Needs Review | |
| 06/15/2005 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 06/15/2005 | GBONILL1 | ENGINEERING | REVIEW | Needs Review |