Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T05CM02493
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/01/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/01/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/02/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM02493 12/1/05 1. Panel Schedule indicates New Panel C. Plans indicate Existing Panel C in Hall, and Single Line Diagram indicates Existing Panel C. Please clarify. 2. Provide Service Disconnect. Reference NEC 230 Part VI. 3. Clarify whether Panels A, B, and C are MLO or MCB. |