Permit Number: T05CM02347
Parcel: 126010720

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM02347
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
11/17/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM02347/8 11/17/05

1. If the fuse at the AC disconnect is intended to provide overload protection, it may have to be sized smaller. (18) (1.25) = 22.5. OR (18) (1.4) = 25.2 If aanufacturer recommends a 35 AF for this unit, disregard.
2. Provide a circuit for the track lighting.
3. Provide size of electric service and service entrance conductors.
4. In Electrical Specifications, please change the wording "2000 INTERNATIONAL RESIDENTIAL CODE" to read "2002 NATIONAL ELECTRICAL CODE."