02/27/2006 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T05CM02137

6/14/05 1832 N. DRAGOON ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN:

1. PLEASE RELOCATE THE SLEEVED GAS LINE FROM UNDER THE BUILDING. SEE THE STATE AMENDMENT FOR UPC 1211.3, EXCEPTION.

FLOOR PLANS:

1. THE SEPARATION OF THE TWO UNITS IS REQUIRED TO EXTEND TO THE ROOF DECK AND THROUGH THE EXTERIOR WALLS TO THE OUTSIDE FACE OF THE WALL. PLEASE SPECIFY 5/8" TYPE "X" DRYWALL. SEE R317.1 .

2. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

STRUCTURAL PLANS:

1. HEADER SCHEDULE / 6 ; THE "H2" HEADER, 2-2X8s, APPEAR TO FAIL AT 6' SPAN. PLEASE JUSTIFY.

2. HEADER SCHEDULE / 6 ; THE 6X8 APPEARS TO FAIL AT 13' SPAN ON THE BACK PORCH. WILL THE TRUSSES BE TWO OR THREE POINT BEARING TRUSSES? ROOF FRAMING NOTE #1 APPEARS TO CONFLICT WITH HEADER SCHEDULE NOTE #2. WHAT GRADE AND SPECIES IS THE PATIO ROOF BEAM? PLEASE JUSTIFY.

3. PROVIDE MANUFACTURER'S DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS.

ELEVATIONS:

1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

SECTIONS - DETAILS - MISC. NOTES:

1. THE SECTIONS ON SHEET 4 REFER TO SHEET 6 FOR THE DETAILS. SHOULD THEY REFER TO SHEET 5?

2. C / 5 ; DESCRIBE THE VERTICAL RE-BAR.

3. PLEASE PROVIDE A CROSS SECTION OF A TYPICAL INTERIOR PARTITION WITH CONNECTIONS.

PLUMBING PLANS:

1. PLUMBING FIXTURE SCHEDULE / 8 ; PLEASE USE THE FIXTURE UNIT VALUES LISTED IN THE U.P.C. SEE TABLE 6-3 . clothes washers are listed as 6 supply f.u. under the '94 upc. the plumbing code on 12/1 was changed to the 2003. Please update your clothes washer's fu and re-check the water distribution sizes. SPECIFY THE WATER METER SIZE.

2. THE WATER DISTRIBUTION SYSTEM APPEARS TO BE UNDER SIZED. SEE ALSO THE WATER HEATER DETAIL. PROVIDE THE MAXIMUM LENGTH. I SCALED IT FROM THE SITE PLAN.

3. INDICATE THE SIZE OF THE WATER LINE TO THE HOSE BIBS AND WHERE IT COMES FROM.

5. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS
AND SHOWERHEADS 3 GALLONS PER MINUTE.

6. SIZE THE GAS PIPING.

7. REMOVE THE GAS UNDER THE FLOOR. IT'S PERMITTED TO BE SLEEVED UNDER A FLOOR ONLY IF IT CAN'T BE AVOIDED.

MECHANICAL PLANS:

1. PLEASE LOCATE AND SIZE THE RETURN AIR DUCT AND FILTER FRAME. SEE M1403.1 AND M1602.2 .

2. PLEASE SIZE THE TRUNK OF THE SUPPLY DUCT.

ELECTRICAL PLANS:

1. THE ELECTRICAL NOTES APPEAR TO CONFLICT. PLEASE SPECIFY THE TYPE OF INSULATION. RECONSIDER THE "TW". IT'S 60 DEGREE INSULATION AND SOME CIRCUITS MAY BE OVER LOADED AFTER AMPACITY CORECTION.the TW insulation is an old designation and is not going to be worth it's full rating in an attic. See nec table 310-16 .

2. THE WALL BETWEEN THE DOOR TO BEDROOM #2 AND THE CLOSET DOOR IS OVER 2 FEET WIDE AND REQUIRES A RECEPTACLE. SEE E3801.2.2 .

3. PLEASE INCLUDE THE MECHANICAL PLAN'S HEAT STRIPS IN THE ELECTRICAL LOAD CALCULATIONS.