Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02116
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 05/11/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/11/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1)RESTROOM FACILITIES NEED TO BE PROVIDED PER CHAPTER 29 TABLE 2902.1 OR SHOW EXISTING FACILITIES AND THE DISTANCED TRAVELED TO EACH FACILITY. 2) CLARIFY RESTROOM FACILITIES THAT MEET ANSI STANDARDS A117.1 2003 ARE PROVIDED. SHOW REQUIRED CLEAR FLOOR SPACE ENVELOPES. |
| 05/11/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/11/2005 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 05/11/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 05/11/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM02116 DENIED 5/11/05 Since the panel is series rates 22/10, specify that the new 10K rated circuit breakers are rated in series with the 22K. |
| 05/17/2005 | CAGUILA1 | WWM | REVIEW | Passed | |
| 05/17/2005 | CAGUILA1 | FIRE | REVIEW | Needs Review |