Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02097
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/21/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | ELECTRICAL DENIED 5/21/05 T05CM02097 1. The note pertaining to the available fault current and rating of equipment appears to be scrambled. It should be revised to read: "All downstream equipment shall be rated to less than 13,900 AIC." 2. Total load is 156A according to load calculations. The 150 A fuse at the service disconnect is sized too small. 3. The 1/0 conductor between the service disconnect and the junction box is undersized. Its ampacity of only 150 A per NEC Table 310.16, 4. Provide conduit and conductor size and type for the run between the junction box and the 10 HP motor. 5. Provide conduit and conductor size and type for the run between the junction box and the 30 HP motor. 6. Check compliance with taps rule in Article 240.21. 7. Specify how overload protection is being provided to both motors per NEC Article 430 Part III. Then check Ground Fault and Short Circuit Protection per NEC 430 Part IV. |
05/25/2005 | GBONILL1 | FIRE | REVIEW | Needs Review | |
05/25/2005 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |