Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM02097
Parcel: 117160130

Address:
35 E TOOLE AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02097
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied ELECTRICAL DENIED 5/21/05 T05CM02097

1. The note pertaining to the available fault current and rating of equipment appears to be scrambled. It should be revised to read: "All downstream equipment shall be rated to less than 13,900 AIC."
2. Total load is 156A according to load calculations. The 150 A fuse at the service disconnect is sized too small.
3. The 1/0 conductor between the service disconnect and the junction box is undersized. Its ampacity of only 150 A per NEC Table 310.16,
4. Provide conduit and conductor size and type for the run between the junction box and the 10 HP motor.
5. Provide conduit and conductor size and type for the run between the junction box and the 30 HP motor.
6. Check compliance with taps rule in Article 240.21.
7. Specify how overload protection is being provided to both motors per NEC Article 430 Part III. Then check Ground Fault and Short Circuit Protection per NEC 430 Part IV.
05/25/2005 GBONILL1 FIRE REVIEW Needs Review
05/25/2005 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/25/2005 GBONILL1 OUT TO CUSTOMER Completed