Permit Number: T05CM02097
Parcel: 117160130

Address:
35 E TOOLE AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02097
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2005 DAVID RIVERA ZONING REVIEW Approved
05/10/2005 DOUG WILLIAMS ENGINEERING REVIEW Approved
05/11/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM02097 DENIED 5/11/05

5/12/05

1. TEP Available Fault Current for 120/208V 200A service is 13900 A per SR-510. Please correct this figure on the plans or justify otherwise.
2. City of Tucson does not allow the Up-Over-Down method of attenuating fault current. Provide fault calculations and fault current rating of disconnect and controller.
3. It is not clear how the motors are being powered. conductor sizes and type, conduit sizes and types, branch circuit overcurrent protective devices, grounding.
4. Provide a detail on what TEP is to attach to. A pole?
05/11/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/11/2005 ROBERT SHERRY WATER REVIEW Passed
05/11/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/20/2005 DHERRON1 FIRE REVIEW Needs Review
05/20/2005 DHERRON1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/20/2005 DHERRON1 OUT TO CUSTOMER Completed
05/20/2005 DHERRON1 OUT TO CUSTOMER Completed