Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02097
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/10/2005 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 05/10/2005 | DOUG WILLIAMS | ENGINEERING | REVIEW | Approved | |
| 05/11/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM02097 DENIED 5/11/05 5/12/05 1. TEP Available Fault Current for 120/208V 200A service is 13900 A per SR-510. Please correct this figure on the plans or justify otherwise. 2. City of Tucson does not allow the Up-Over-Down method of attenuating fault current. Provide fault calculations and fault current rating of disconnect and controller. 3. It is not clear how the motors are being powered. conductor sizes and type, conduit sizes and types, branch circuit overcurrent protective devices, grounding. 4. Provide a detail on what TEP is to attach to. A pole? |
| 05/11/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/11/2005 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 05/11/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 05/20/2005 | DHERRON1 | FIRE | REVIEW | Needs Review | |
| 05/20/2005 | DHERRON1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/20/2005 | DHERRON1 | OUT TO CUSTOMER | Completed |
| 05/20/2005 | DHERRON1 | OUT TO CUSTOMER | Completed |