Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM01903
Parcel: 141148180

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01903
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
05/17/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/17/2005 ANY BUILDING-COMMERCIAL REVIEW Approved
05/17/2005 ROBERT SHERRY WATER REVIEW Approved
05/17/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/10/2005 TERRY STEVENS ZONING REVIEW Approved
06/10/2005 GERRY KOZIOL WWM REVIEW Approved
06/10/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM01903 DENEID 5/17/05

1. Panel schedule has 62096 VA of lighting. Load calculations only have 8096. Please clarify.
2. Ckts A-12 and A-14 have lighting, on panel schedule, but no loads. Clarify.
3. Plot location of Panel A on plans. This may be critical to determine whether the 10,000 A fault current rating is appropriate.
4. With the addition of the track lighting, demonstrate compliance with the 2000 IECC.
06/10/2005 JIM EGAN FIRE REVIEW Approved