Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01903
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/17/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 05/17/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/17/2005 | ANY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/17/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/17/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 06/10/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 06/10/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/10/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM01903 DENEID 5/17/05 1. Panel schedule has 62096 VA of lighting. Load calculations only have 8096. Please clarify. 2. Ckts A-12 and A-14 have lighting, on panel schedule, but no loads. Clarify. 3. Plot location of Panel A on plans. This may be critical to determine whether the 10,000 A fault current rating is appropriate. 4. With the addition of the track lighting, demonstrate compliance with the 2000 IECC. |
| 06/10/2005 | JIM EGAN | FIRE | REVIEW | Approved |