Permit Number: T05CM01898
Parcel: 13819045B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM01898
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2005 GERRY KOZIOL WWM REVIEW Approved
06/16/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the required Outdoor Air Intake for HP-1 (shown as HP-2 on sheet M202) and HP-2 per Section 6.2.4.4, ASHRAE 62-2001, Addendum n. Reference Section 6.2.4, ASHRAE 62-2001, Addendum n.
06/16/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The detail of the two-way GCO does not comply with Section 707.6, UPC 1994.
2. Detail 2/P201 still shows ¾" runouts to the urinals, which is unsupported by the calculations and the maximum water velocity.
06/29/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
07/08/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
07/20/2005 TERRY STEVENS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/21/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
07/21/2005 SUE REEVES REJECT SHELF Completed