Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM01898
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/14/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/16/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the required Outdoor Air Intake for HP-1 (shown as HP-2 on sheet M202) and HP-2 per Section 6.2.4.4, ASHRAE 62-2001, Addendum n. Reference Section 6.2.4, ASHRAE 62-2001, Addendum n. |
| 06/16/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The detail of the two-way GCO does not comply with Section 707.6, UPC 1994. 2. Detail 2/P201 still shows ¾" runouts to the urinals, which is unsupported by the calculations and the maximum water velocity. |
| 06/29/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/08/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/20/2005 | TERRY STEVENS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/21/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 07/21/2005 | SUE REEVES | REJECT SHELF | Completed |