Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM00922
Parcel: 11711064C

Address:
101 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00922
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2005 JIM EGAN FIRE REVIEW Approved
03/14/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Non-metallic sheathed cable not approved for this application. Reference NEC 334.10 (3) and 527.4 (B). Suggest the use of flexible metallic conduit.
2. It appears that there is a spurious note by Grid Point G-6. Repeats the one directly below and no arrowhead.
3. Sheet E-1 fuse size for Temporary Cooling Tower is listed as 17.5 A. Could the intent be to provide a 15AF.
03/25/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 3/29/05
ACTIVITY NUMBER: T05CM00922
PROJECT NAME: Replace Cooling Tower
PROJECT ADDRESS: 101 N. Stone Ave.
ARCHITECT / ENGINEER: Schneider & Assoc. Engineers
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Clarify dead loads for new equipment drawing S1 and structural calculations contradict each other.
2) Sht. 7 structural calculations summary states column is under reinforced. Justify existing columns can carry new loads.
3) Dimension S1 drawing - Clarify support system carrying load to the ground.
04/04/2005 ROBERT SHERRY WATER REVIEW Approved
04/04/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the drain from the temporary location of the cooling tower to terminate over an indirect waste receptor instead of a direct connection. Reference Section 801.1, UPC 1994.
04/04/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2005 DELMA ROBEY OUT TO CUSTOMER Completed