Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05CM00873
Parcel: 11507315B

Address:
25 E DRACHMAN ST

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM00873
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/28/2005 LAITH ALSHAMI ENGINEERING REVIEW Approved
02/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide the total load and developed length for the existing gas service.
02/28/2005 DAN CASTRO ZONING REVIEW Approved
03/08/2005 DROBEY1 FIRE REVIEW Needs Review
03/08/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM00873 DENIED 2/28/05

1. Per NEC 250.32, two or more buildings or structures supplied from a common service shall have a Grounding Electrode System installed, or be tied to one which is existing. On the One Line Diagram, please eliminate the wording "(Omit for alternate bid)" by the grounding symbol.
2. On the One Line Diagram, please eliminate the #6 GRD between the TEP X'FMR and the service disconnect as a redundant path to ground.
3. Please coordinate with Mechanical regarding MOCP for the CU units. According to the Condensing Unit Schedule, MOCP is 24, an unusual number. Electrical has them fused at 40A.