Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T05CM00873
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/28/2005 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
| 02/28/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide the total load and developed length for the existing gas service. |
| 02/28/2005 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 03/08/2005 | DROBEY1 | FIRE | REVIEW | Needs Review | |
| 03/08/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM00873 DENIED 2/28/05 1. Per NEC 250.32, two or more buildings or structures supplied from a common service shall have a Grounding Electrode System installed, or be tied to one which is existing. On the One Line Diagram, please eliminate the wording "(Omit for alternate bid)" by the grounding symbol. 2. On the One Line Diagram, please eliminate the #6 GRD between the TEP X'FMR and the service disconnect as a redundant path to ground. 3. Please coordinate with Mechanical regarding MOCP for the CU units. According to the Condensing Unit Schedule, MOCP is 24, an unusual number. Electrical has them fused at 40A. |