Permit: T05CM00873
Permit Details
Apply Date:
02/28/2005
Applicant:
MECHANICAL MAINTENANCE INC ,
Description:
DEHUMIDIFICATION UNIT
Contractors:
- MECHANICAL MAINTENANCE INC ,
Permit Reviews
Permit Number - T05CM00873
Permit Status: C of o
Permit Description: DEHUMIDIFICATION UNIT
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/28/2005 | OTHER | 03/08/2005 | COMPLETED |
| 03/08/2005 | RESUBMITTAL | 03/08/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05CM00873
Permit Status: C of o
Permit Description: DEHUMIDIFICATION UNIT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 02/28/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T05CM00873
Permit Description: DEHUMIDIFICATION UNIT
Total Completed Inspections - 13
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2005 | ELECTRIC - UNDERGROUND | RMAJUTA | Approved | IVRS - Inspection :* NOTE: THE #4 GROUND TO NEW SERVICE IS ATTACHED TO THE WATER PIPE, ITMUST ALSO BE TIED DIRECTLY TO THE GROUND WIRE TO ORIGINAL SERVICE, 250-58 2002 NEC ALSO FOR FINAL ALSO PLEASE INSTALL AN ADDRESS LABEL ON NEW SERVICE. |
| 03/16/2005 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | IVRS - Inspection :* 1) ROUGH GAS PIPING FROM METER LOCATION TO UNIT LOCATION OK PRESSURE TEST OK. NEED TO SEE ALL FINAL CONNECTIONS ON FINAL. |
| 04/21/2005 | MECHANICAL - INTERMEDIATE | CWILLIAM | Approved | IVRS - Inspection :* |
| 04/21/2005 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | IVRS - Inspection :* |
| 04/21/2005 | FIRE - FINAL | CSCHULTZ | Approved | |
| 04/21/2005 | FIRE SPKLR - FINAL | CSCHULTZ | Approved | |
| 05/05/2005 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* 1) CORRECTIONS MADE OK. 2) PLUMBING FINAL OK. 3) OK TO ACTIVATE GAS. OK FOR C OF O STOI |
| 05/05/2005 | TEP CLEARANCE - AM | JKOZUCH | Approved | ECO PER BETH GRANT |
| 11/03/2005 | MECHANICAL - FINAL | CWILLIAM | Approved | IVRS - Inspection :*DRY WELL SUMP OK |
| 11/03/2005 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
| 11/10/2005 | PERMIT FINALED | LJACKSON | Approved | |
| 11/10/2005 | BUILDING - FINAL | AQUIROZ | Approved | PER PH CALL |
| 11/14/2005 | ELECTRIC - FINAL | RMAJUTA | Approved | NEED APPROVED LISTING ON DEHUMIDIFIER. FINAL SUBJECT TO ETL LISTING ON DEHUMIDIFIER. I WAS ASKED OT RELEASE POWER BY DAVE MANN WHILE THIS WAS GOING ON |