Permit Number: T05CM00872
Parcel: 115062050

Address:
1801 N STONE AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM00872
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Wildcat House Site Improvements
T05CM00872
Building Plan (1st Review)

TRANSMITTAL DATE: June 5, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Per COT DSD Administration this plan must be approved prior to July 3, 2008 or new review fees will be required.

4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t05cm00872.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
06/16/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: June 16, 2008
SUBJECT: Site Improvements
TO: ADG
LOCATION: 1801 N Stone Ave, T14S, R13E, Section 1, Ward 3
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07CM00872


RESUBMITTAL REQUIRED: Site Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.


Site Plan:


1. Please include a response letter to the comments along with the corrected copies of the Site Plan.
2. Complied
3. Complied
4. Complied
5. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. Revise SVT dimensions for SVT(s) along N. Stone Ave going north from W. Lester Street.
7. Within southeast corner of parcel there appears to be a line that may have been intended to be a sight visibility triangle. See plans and clarify and/or modify accordingly.
8. DS Sec.2-02.2.1.A.10: Verify that all existing and future site visibility triangles (SVT) are labeled and dimensioned.
9. Label parking area access lanes P.A.A.L.(s) and include dimensions as shown on plan per D.S. 2-02.2.1.11.
10. Complied
11. Complied
12. Complied
13. Fully dimensioned loading space(s) and maneuvering area(s) in plan view per D.S. 2-02.2.1.14. DS Sec.2-02.2.1.A.14: Provide (label and dimension) the required onsite maneuvering area for the loading zone. Refer to AASHTO for the national standards for turning radii and indicate appropriate radaii on site plan.
14. Provide Drainage patterns and finished grades per D.S. 2-02.2.1.16. Drainage patterns and finished grades appear to be located on the grading plan. Indicate on site plan - detail does not need to be as detailed as the grading plan per D.S. 2-02.2.1.16. Show general flow of drainage.
15. Complied
16. DS Sec.2-02.2.1.A.19: Dimension the 10-foot future sidewalk and curb area on the site plan.
17. Complied
18. Complied
19. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23. Indicate existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number on site plan per D.S. 2-02.2.1.23
20. Complied
21. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. See the attached refuse detail for minimum requirements. Provide detail for trash enclosure to site plan.
22. DS Sec.2-02.2.1.A.32: Label and show the maneuverability for refuse vehicles in plan view at the proposed refuse container location.
23. Complied
24. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
25. Provide a typical cross section of the P.A.A.L. or call out the percentage of slopes. Provide information on the site plan.
26. Complied
27. On hadicap sign T.C.C. 29-222 should read T.C.C. 20-222.
27. Additional comments may be forthcoming.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax