Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T05CM00552
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/07/2005 | MATT FLICK | ENGINEERING | REVIEW | Denied | Need floodplain review approval prior to this approval. |
| 12/07/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/07/2005 | JIM EGAN | FIRE | REVIEW | Denied | 1. PANIC HARDWARE REQUIRED ON EXIT DOORS. INDICATE LOCATION ON PLAN. 2. MANUAL FIRE ALARM SYSTEM REQUIRED. 3. OCCUPANCY IS NOT "E". (A-3) DETERMINE OCCUPANT LOAD BASED ON ASSEMBLY USE. |
| 12/07/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/22/2005 | HEATHER THRALL | ZONING | REVIEW | Denied | Zoning cannot approve the building plans until a site plan has been approved for this project. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/28/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 12/28/2005 | SUE REEVES | REJECT SHELF | Completed |