Review Details: COMMERCIAL TI

Permit Number - T05CM00494
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
02/08/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/08/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE VALUATION
2) RESTROOM FACILITIES NEED TO MEET ANSI A117.1 2003 STANDARDS OR PROVIDE JUSTIFICATION THAT 20% COST OF CONSTRUCTION IS BEING SPENT TOWARDS MEETING THE STANDARDS.
3) PROVIDE CONNECTORS FOR DEMISING WALL BRACING TO EXISTING STRUCTURE.
4) CLARIFY SQ. FOOTAGE CALCULATIONS EXISTING BUILDING IS LESS THAN THE ALLOWABLE SQ. FOOTAGE.
02/08/2005 ROBERT SHERRY WATER REVIEW Approved
02/08/2005 DAN CASTRO ZONING REVIEW Approved
02/08/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations to show that the projet has adequate ventilation. Reference Section 403.3, IMC 2000.
02/08/2005 JIM EGAN FIRE REVIEW Approved
02/11/2005 DROBEY1 WWM REVIEW Needs Review
02/11/2005 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review T05CM00494 DENIED 2/8/05

Provide fault calculations to demonstrate that Panel B has the proper fault current rating in its' new position, or justify otherwise.