Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00494
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/04/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
02/08/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
02/08/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE VALUATION 2) RESTROOM FACILITIES NEED TO MEET ANSI A117.1 2003 STANDARDS OR PROVIDE JUSTIFICATION THAT 20% COST OF CONSTRUCTION IS BEING SPENT TOWARDS MEETING THE STANDARDS. 3) PROVIDE CONNECTORS FOR DEMISING WALL BRACING TO EXISTING STRUCTURE. 4) CLARIFY SQ. FOOTAGE CALCULATIONS EXISTING BUILDING IS LESS THAN THE ALLOWABLE SQ. FOOTAGE. |
02/08/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/08/2005 | DAN CASTRO | ZONING | REVIEW | Approved | |
02/08/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide calculations to show that the projet has adequate ventilation. Reference Section 403.3, IMC 2000. |
02/08/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
02/11/2005 | DROBEY1 | WWM | REVIEW | Needs Review | |
02/11/2005 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | T05CM00494 DENIED 2/8/05 Provide fault calculations to demonstrate that Panel B has the proper fault current rating in its' new position, or justify otherwise. |