Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00263
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/21/2005 | ANY | ENGINEERING | REVIEW | Approved | |
| 01/21/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. For use as a unisex children's restroom, the water closets must be child size. 2. The minimum trap size for a service sink is 2". 3. Show the return hot water piping on the isometric. |
| 01/21/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM00263 DENIED 1/21/05 1. Water Heater OCPD per NEC 422.11 (E) (3), should not exceed (4000)/240 * 1.5 = 25A. 2. Please provide disconnect for Water Heater per NEC 422 Part III. This could be done by specifying that the breaker be capable of being locked in the open position. (422.30 (B). 3. Heat pump disconnects are specified at 20A, typical. Heat pumps MCA 26.1 and 34.9. Please clarify. 4. Please note that only if the existing service is overhead may the new service be overhead. Otherwise, provide underground service. |
| 01/21/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/21/2005 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 01/21/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the outside air calculation for AC-3 per Section 403.3.2, IMC 2000. 2. Provide calculations to show that the temperature in the building can be maintained at 68 degrees Fahrenheit on a design day. |
| 01/27/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 01/27/2005 | TACHONG1 | WWM | REVIEW | Needs Review | |
| 01/27/2005 | TACHONG1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/27/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |