Review Details: COMMERCIAL TI

Permit Number - T05CM00263
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2005 ANY ENGINEERING REVIEW Approved
01/21/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. For use as a unisex children's restroom, the water closets must be child size.
2. The minimum trap size for a service sink is 2".
3. Show the return hot water piping on the isometric.
01/21/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM00263 DENIED 1/21/05
1. Water Heater OCPD per NEC 422.11 (E) (3), should not exceed (4000)/240 * 1.5 = 25A.
2. Please provide disconnect for Water Heater per NEC 422 Part III. This could be done by specifying that the breaker be capable of being locked in the open position. (422.30 (B).
3. Heat pump disconnects are specified at 20A, typical. Heat pumps MCA 26.1 and 34.9. Please clarify.
4. Please note that only if the existing service is overhead may the new service be overhead. Otherwise, provide underground service.
01/21/2005 ROBERT SHERRY WATER REVIEW Approved
01/21/2005 PATRICIA GEHLEN ZONING REVIEW Approved
01/21/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the outside air calculation for AC-3 per Section 403.3.2, IMC 2000.
2. Provide calculations to show that the temperature in the building can be maintained at 68 degrees Fahrenheit on a design day.
01/27/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Needs Review
01/27/2005 TACHONG1 WWM REVIEW Needs Review
01/27/2005 TACHONG1 FIRE REVIEW Needs Review