Permit Number: T05CM00155
Parcel: 127042870

Address:
4920 E BAKER ST

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T05CM00155
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2005 GERRY KOZIOL WWM REVIEW Approved
03/16/2005 ANDREW CONNOR NPPO REVIEW Passed
03/24/2005 HEATHER THRALL ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Heather Thrall Senior Planner FOR: David Rivera Principal Planner

PROJECT: T05CM00155
4920 E. Baker Street
Single Family Residential additions, conversion of garage to inhabitable area
Site plan
1st Review
Transmittal date: March 25, 2005


COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Please dimension the elevation drawings to allow height and setback requirements to be verified.

2. The submitted plans shows a new kitchen will be added to the existing residence. Please clarify if the existing kitchen is to be removed, and what type of new use this area of the residence will have.

3. Please provide staff with a floor plan and elevations of the garage structure to be converted to a guest quarters. Dimensions, exterior wall heights, total building heights and uses for each room should be shown for the structure. The square footage of the structure should also be added to the site plan notes and lot coverage calculations.

4. Please be advised, depending upon the information shown on the guest house conversion floor plan, paved and striped parking with barrier provisions may need to be provided for the site in the rear or side yard. This code information can be found in section 3.5.7.1.G & H of the Land Use Code. The parking area would need to conform to Development Standard 3-05.0

5. The conversion of the existing garage to a habitable area requires the structure meet current zoning code requirements, such as setbacks. The required setback for the south property line is equivalent to the height of the exterior building wall of the structure facing that property line. Based upon the setback provided on the site plan of 4.33 feet, the structure would not meet this requirement. To seek permission for this reduced setback, a Lot Development Option (LDO) would be required.

6. These are not final LDO referral comments. Once the site plan has been revised to show the above requested information, final LDO comments can be made. For final LDO comments, please contact me via email at Heather.Thrall@tucsonaz.gov or at 520-791-5608x1156 to make an office appointment.


If you have any questions about this transmittal, please call (520) 791-5608.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/30/2005 DELMA ROBEY OUT TO CUSTOMER Completed