Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - GRADING
Permit Number - T05BU00460
Review Name: RESUBMITTAL - GRADING
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/03/2008 | DAVID RIVERA | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: David Rivera PROJECT: Wildcat House Site Improvements T05BU00460 Grading Plan (4th Review) TRANSMITTAL DATE: , 2007 1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal. 3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please call Steve Shields, (520) 791-5608 ext. 1180. C:\planning\grading\t06bu00460.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plan and additional requested documents |
06/06/2008 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | Site plan approval is necessary to continue review. |
06/17/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Denied | DATE: June 17, 2008 SUBJECT: Site Improvements TO: ADG LOCATION: 1801 N Stone Ave, T14S, R13E, Section 1, Ward 3 REVIEWERS: Bianca Ramirez, CFM ACTIVITY: T05BU00460 RESUBMITTAL REQUIRED: Grading Plan SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed grading plan for the above referenced property. Engineering Division does not recommend approval of the grading plan at this time. Please address the following review comments prior to the next submittal. Due to the expiration of the permit and the length of time between reviews. The Engineering Department will be looking at the submittal as a first time review. Additional comments have been provided for current compliance for grading plan. Please include a response letter to the comments along with the corrected copies of the Grading Plan. Grading Plan: 1. A copy of the stamped approved site plan must be included with the grading plan. It is acknowledged that the site plan is currently in review. Be advised that any changes made to the site plan must be reflected on the grading plan. The site plan and the grading plan must match. 2. Complied 3. Complied 4. Add and modify all sight visibility triangles accordingly. 5. Complied 6. Complied 7. Complied 8. Show cross section with transverse and longitudinal slopes. 9. Complied 10. DS Sec.2-02.2.1.A.10: Provide on grading plan existing and future site visibility triangles (SVT) are labeled and dimensioned. 11. Dimension on grading plan all points of egress and ingress including locations and width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11. and label on site plan. 12. DS Sec.2-02.2.1.A.11 & DS Sec.3-01.3.2.C: Depict and label 18-feet radii concrete curbs per City of Tucson/Pima County Standard Detail 213 (PC/COT SD 213) at the driveway entrance along West Plata Street and also at north entrance along North Ninth Avenue. The curbs should be constructed at the edge of pavement and entirely on the subject property. Provide on the grading plan. 13. DS Sec. 2-05.2.4.H.2: Provide the right-of-way (ROW) recordation information for North Stone Ave, West Plata Street, North Ninth Avenue and West Lester Street on grading plan. 14. DS Sec.2-02.2.1.A.19: Label the 10-foot future sidewalk and curb area on the site plan to verify that all improvements are located outside of the future ROW on the grading plan. 15. Complied 16. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines on grading plan per D.S. 2-02.2.1.21. 17. Provide existing topographic contours at intervals not exceeding two (2) feet. Legend indicates existing and new contours - unable to locate new contour line. Provide explanation as to where the contours differentiate. 18. Complied 19. Complied 20. Complied 21. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information. 22. Complied 23. Verify that all text is readable - adjust areas where text is overlapping. 24. Verify that all text is a minimum of twelve (12) point font. 25. Additional comments may be forthcoming. If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov Bianca C. Ramirez Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 837-4928 office (520) 879-8010 fax |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/02/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |