Permit Number: T05BU00460
Parcel: 115062050

Address:
1801 N STONE AV

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T05BU00460
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2006 SUZANNE BOHNET ENGINEERING REVIEW Denied 1. Grading Plan cannot be approved without an approved Site Plan. Site Plan resubmitted but not yet approved.
2. Drainage Report not submitted for re-review. Please submit the complete drainage package.
3. Additional comments may be forthcoming until Site Plan is approved.

Suzanne Bohnet, CFM
Engineering Associate
791-5550 x1188
Suzanne.Bohnet@tucsonaz.gov
09/28/2006 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Wildcat House Site Improvements
T05BU00460
Grading Plan (1st Review)

TRANSMITTAL DATE: September 29, 2006

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please call Steve Shields,
(520) 791-5608 ext. 1180.

C:\planning\grading\t06bu00460.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plan and additional requested documents
09/29/2006 ANDREW CONNOR NPPO REVIEW Denied Submit a copy of the approved site plan including landscape plan for reference. The grading application will be reviewed for compliance only when the approved documents are included in the submittal. Revise grading plans as necessary to comply with the approved site plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/11/2006 DELMA ROBEY OUT TO CUSTOMER Completed
10/11/2006 SUE REEVES REJECT SHELF Completed