Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04OT00938
Parcel: 13816024A

Address:
331 E ELVIRA RD

Review Status: Completed

Review Details: SITE

Permit Number - T04OT00938
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2004 JIM EGAN FIRE REVIEW Denied 1. Fire apparatus access roadway must be provided and extended to within 150 feet of all portions of the exterior walls of all structures. An approved turnaround must be provided for dead-end access roadways.
2. Show location of nearest fire hydrant on plan.
06/10/2004 DAN CASTRO HANDICAP-SITE REVIEW Approved
06/10/2004 Daniel Castro ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next
submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.
CODE SECTION/ DEVELOPMENT STANDARD

1. Revise the building height noted in each of the four duplexes from 8 feet to 12 feet. The maximum height noted under the zoning information block on sheet 1 is 12 feet. (D.S. 2-02.2.1.A.6)

2. Provide the elevation drawings for the building/s proposed. Elevation drawings shall have the heights dimensioned from design grade. In addition, be sure to note the exterior building wall heights measured from design grade and not finished floor elevation. This is required to verify building setback requirements. (D.S. 2-02.2.1.A.7) (LUC 3.2.7.2.A)

3. Remove the reference to activity number "T03-M0053". What does this activity number refer to? It does not appear to have any relevance to this project.

4. Review of this plan by the Zoning Review Section may be done over the counter. Please contact Dan Castro to set an appointment.


If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.
06/11/2004 JOE LINVILLE NPPO REVIEW Denied Identify all protected plants on the site. Provide data on plant size. DS 2-15.0
06/11/2004 Joseph Linville LANDSCAPE REVIEW Denied 1) A 5' high masonry screen wall is required on the eastern property line to screen the vehicular use area from the adjacent residentially zoned parcel. Revise the landscape plan call-out to specify a masonry wall. Show the required wall on the site plan also. DS 2-02.2.1

2) Revise the landscape plan note regarding decomposed granite to include the area between the property line and the curb, if no sidewalk is required. Material for this pedestrian area is to include compacted 1/4" minus DG.

3) Revise the landscape plan to use matching symbols in the legend and on the plan. DS 2-07.2.2

4) Show irrigation water source, mainlines, sleeving.
DS 2-06.5.4

5) Revise the planting plan to locate plants taller than 30" outside of applicable sight visibilty triangles. DS 3-01.5.0

6) Identify all existing plants on the landscape plan.
DS 2-07.2.2 Mitigation plantings may be required in order to comply with native plant preservation requirements.
06/29/2004 Loren Makus ENGINEERING REVIEW Denied June 29, 2004
Lanier 4-Duplex Project
Reviewer: Loren Makus, EIT
Activity Number: T04OT00938

The Site Plan cannot be approved at this time. Revise the site plan as follows.
Give the correct dimensions on the sight visibility triangles. The near side SVT should be 20 feet by 185 feet. The far side SVT should be 20 feet by 110 feet.

I am willing to review your revised plans over the counter. Please call to set up an appointment 520.791.4440 ext 1161

Final Status

Task End Date Reviewer's Name Type of Review Description
06/30/2004 LISA LESNY OUT TO CUSTOMER Completed
06/30/2004 ANGIE SHOFFSTALL REJECT SHELF Completed