Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04EL02176
Parcel: 127121200

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T04EL02176
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04EL02176 DENIED 10/27/04

1. Provide available fault current at service.
2. Provide fault calculations for AFC at existing sub-panel.
3. Specify fault current rating of sub-panel.
4. Fault current rating of new disconnect is 10000 AIC, whereas response to original comment indicates that the AFC at POA is 15,426.
5. On electrical site plan, plot locations of all new equipment, including HVAC units and disconnects, and of existing sub-panel.
6. Provide power requirements for new HVAC units.
7. Provide panel and circuit number for all new equipment.
8. Provide panel schedule for new panel. See the attached Electrical Permitting Requirements.
9. Provide maintenance receptacles for all new AC units per NEC 210.63, or justify otherwise.