Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T04EL02176
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/27/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04EL02176 DENIED 10/27/04 1. Provide available fault current at service. 2. Provide fault calculations for AFC at existing sub-panel. 3. Provide conductor size and type for sub-panel feeder. 4. Provide overcurrent protection for sub-panel feeder. Specify voltage, number of poles, amps, and fault current rating. 5. Specify fault current rating of sub-panel. 6. Specify size of the Grounding Electrode Conductor. 7. Provide electrical site plan, with locations of all new and existing equipment in plan view. 8. If building is over 3000 SF or continuously occupied by greater than 20 persons, plans shall be prepared and sealed by an Architect or Engineer registered in the State of Arizona. |