Permit Number - T04CM05406
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM05406 DENIED 12/15/04
1. Registrant shall seal, sign, and date plans.
2. Please re-evaluate fault current rating of new Panel A. It is just on the other side of the wall from a 600A service rated 65K.
3. Note 1 should refer to the 2002 NEC, not the 1999.
12/15/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/15/2004 ROBERT SHERRY WATER REVIEW Approved
12/15/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/16/2004 TACHONG1 FIRE REVIEW Needs Review
12/16/2004 TACHONG1 WWM REVIEW Needs Review
12/16/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE ATTACHMENT/SEISMIC DETAIL FOR ACOUSTICAL CEILING TO EXISTING STRUCTURE. INTERIOR ROOF HEIGHT?
12/16/2004 TACHONG1 ZONING REVIEW Needs Review
12/16/2004 TACHONG1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/16/2004 TAMI ACHONG OUT TO CUSTOMER Completed