Review Details: COMMERCIAL TI
Permit Number - T04CM05406
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/15/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM05406 DENIED 12/15/04 1. Registrant shall seal, sign, and date plans. 2. Please re-evaluate fault current rating of new Panel A. It is just on the other side of the wall from a 600A service rated 65K. 3. Note 1 should refer to the 2002 NEC, not the 1999. |
| 12/15/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 12/15/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/15/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/16/2004 | TACHONG1 | FIRE | REVIEW | Needs Review | |
| 12/16/2004 | TACHONG1 | WWM | REVIEW | Needs Review | |
| 12/16/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE ATTACHMENT/SEISMIC DETAIL FOR ACOUSTICAL CEILING TO EXISTING STRUCTURE. INTERIOR ROOF HEIGHT? |
| 12/16/2004 | TACHONG1 | ZONING | REVIEW | Needs Review | |
| 12/16/2004 | TACHONG1 | ENGINEERING | REVIEW | Needs Review |