Permit Number: T04CM05376
Parcel: 141148150

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05376
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Limit the water velocity to less than 8 fps for the copper piping (e.g. HWR). Reference Section A 6.1, UPC 1994 and IAPMO IS 3-93, Section 610.0.
2. Coordinate the waste & vent riser diagram with the plumbing floor plan.
02/04/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/07/2005 JIM EGAN FIRE REVIEW Approved
02/09/2005 CAGUILA1 WWM REVIEW Needs Review
02/09/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TO4CM05376 DENIED 2/7/05
1. On Plans WH is indicated to be on Ckt 33-34-36. Please correct to 32-34-36 per panel schedule.
2. WH is 18 KW 3-phase 50 A per Electrical Schedule Sheet E1.1. Is 60 KW single phase 28.8 a per Sheet P2. Please coordinate with Mechanical and clarify.
3. Plumbing references RCP-1 Recirc Pump on Shts P1 and P2. Please provide electrical power.
4. Suggest a re-evaluation of the 60 AF at the HP disconnect, considering that it is protected upstream by a 50 A CB.
02/09/2005 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review